Niko 360-45011 Mode D'emploi page 48

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

360-45011
390-40011
module.
- Factory: In this mode, the daylight control module operates according to the fabric settings. You
can only view these settings, you can not modify them.
Select operating mode with or without DIM memory:
- With DIM memory: If the system switches from automatic to manual mode, the light level in all
active channels is identical to the light level at the moment the manual mode has been exited.
- Without DIM memory: If the system switches from automatic to manual mode, the light level is
max. in all active channels.
4.2. Adjustment (see 'Quickguide', B, C and D)
In this menu, you can:
Set the daylight factor:
The daylight factor is the relation between the actual daylight level (lx ind) in a zone and the
daylight level measured by the light sensor. The parameters for the daylight factor should be
measured at a moment of the day when there is sufficient daylight and there is NO influence of
artificial light. Parameters:
- Range (bereik): standard 30-30klx
- Lx ind X: Insert the daylight level you measure by a lux meter in the different zones (1, 2, 3).
Preferably measure the daylight level at table height.
- Sensor: Insert the daylight level the sensor (placed by the window) measures. The displayed sensor
value is a snapshot of the actual sensor value at the moment you opened this sub menu.
Adjust CH X:
In these 3 sub menus, you can set the parameters per channel (CH).
- Setp X: Setpoint. This is the min. light level that is actually required in a zone zone (1, 2, 3).
If there is sufficient daylight, the lighting is switched on and is dimmed to the desired light
level (setp).
- Vout min X: adjustable between 0 – 4V; standard 0V
48
EN

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

390-40011

Table des Matières