Time switch 420-00200 + 1XX-78200
Depending on the application (see 3.4), you can connect a time switch in order to switch the
lighting on and off.
Single-pole switch 170-01100
Youy can connect an energy-saving switch (loadshedding --> see '4.2 ADJUSTMENT') to the
daylight control module in order to limit the maximum lighting.
4-fold push button with feedback LEDs 170-40100
For every application (see 4.4), you can connect a 4-fold push button with feedback LEDs. Only 2
of the 4 push buttons with feedback are used, because the module can only switch the lighting:
- Auto (with feedback): The system goes to automatic mode, the lighting is daylight controlled
according to the settings of the application.
- I/O (with feedback): 'on-off'. The system is set to manual mode. You can switch the lighting on or
off by pressing the push button. If the lighting is switched on, it is NOT daylight controlled, but is
switched on in all areas (Unless the DIM memory function is activated, see 5.1 'general set').
- The other 2 push buttons are used for simultaneously dimming up and down the lighting in all
zones (1-10V control). These two push buttons have no feedback. When dimming, the system
is always set to manual mode.
3.4 Applications
The daylight control module is provided with a number of preprogrammed applications you can
select as a standard (fig.3). For selecting an application, see 'Quickguide', A.
Application 10.01 (fabric setting):
Automatic DIM via motion sensor (fig.4a)
If the motion sensor detects activity and there is a need for daylight, the 3-channel daylight module
is switched on. As long as the motion sensor detects activity, the light is controlled in 3 channels
in accordance with the set parameters. As daylight incidence increases/decreases, the light dims
down/up in the premises in order to reach the required, min. light level. If the motion sensors do
not detect movement, or if a sufficient light level has been reached in the room, the light switches
EN