Honeywell RedLINK Guide D'installation page 9

Masquer les pouces Voir aussi pour RedLINK:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installer setup tables
Setup function
0
Zone number
1
System type
2
Changeover valve
(O/B terminal)
3
Fan control
(conventional heat)
4
Backup heat (Aux &
EmHeat)
5
Stage 1 heat cycle
rate (CPH: cycles/
hour)
6
Stage 2 heat cycle
rate (CPH)
7
Stage 3 heat cycle
rate (CPH)
8
Emergency heat cycle
rate (CPH)
9
Stage 1 compressor
cycle rate
10
Stage 2 compressor
cycle rate
11
Heat pump type
12
Manual/Auto
changeover
13
Adaptive Intelligent
Recovery™
14
Temperature
display
69-2091EFS_C.indd 9
Français : voir la page 21 • Español: vea la página 41
Settings & options (factory default in bold)
0
No zoning (single thermostat used with THM5320R EIM)
[Options: select zone 1, 2, 3 or 4]
0
1 heat/1 cool conventional
1
1 heat/1 cool heat pump (no aux. heat)
2
Heat only (includes Series 20)
3
Heat only with fan
4
Cool only
5
2 heat/1 cool heat pump
6
2 heat/2 cool conventional
7
2 heat/1 cool conventional
8
1 heat/2 cool conventional
9
2 heat/2 cool heat pump
10
3 heat/2 cool heat pump
0
O/B terminal controls valve in cooling
1
O/B terminal controls valve in heating
0
Gas/Oil heat (equipment controls fan)
1
Electric furnace (thermostat controls fan)
1
Electric backup heat
0
Fossil fuel backup heat
5
Gas or oil furnaces (less than 90% efficiency)
1
Steam or gravity systems
3
Hot water systems & furnaces of over 90% efficiency
9
Electric furnaces
[Cycle rate options: 1 to 12 CPH]
5
Gas or oil furnaces (less than 90% efficiency)
1
Steam or gravity systems
3
Hot water systems & furnaces of over 90% efficiency
9
Electric furnaces
[Cycle rate options: 1 to 12 CPH]
5
Gas or oil furnaces (less than 90% efficiency)
1
Steam or gravity systems
3
Hot water systems & furnaces of over 90% efficiency
9
Electric furnaces
[Cycle rate options: 1 to 12 CPH]
9
Electric furnace
[Cycle rate options: 1 to 12 CPH]
3
Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
3
Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
0
Air to Air Heat Pump
1
Geothermal heat pump
0
Manual (User options: Heat/Cool/Off)
1
Automatic (User options: Heat/Cool/Auto/Off)
Applies only to Model TH6320
1
On
0
Off
0
Fahrenheit
1
Celsius
9
69-2091EFS—05
3/11/2009 12:52:51 PM

Publicité

Chapitres

Table des Matières
loading

Table des Matières