R7284B,P,U,G
Electronic Oil Primary,
EnviraCOM™ Enabled
APPLICATION
The R7284B,P,U,G Electronic Oil Primary is a line
voltage, safety rated, interrupted and intermittent ignition
oil primary control for residential oil fired burners used in
boilers, forced air furnaces and water heaters. The
R7284B,P,U,G used with a cad cell flame sensor
operates an oil burner, spark igniter, and optional oil
valve. The control works with a low voltage and optional
high voltage thermostat. The primary controls fuel oil,
senses flame, controls ignition spark (either interrupted
or intermittent) and notifies through the EnviraCOM™
bus a remote alarm circuit when in lockout.
The R7284 Series of Oil Primary Controls can be used
with both hydronic and forced air systems. When used
with hydronic systems, line voltage switching Aquastat®
Controllers normally provide for the starting and stopping
of the combustion sequences. With forced air systems,
both mechanical and electronic low voltage thermostats
control the starting and stopping of the combustion
process.
Some hydronic and forced air systems require a delayed
valve-on and burner motor-off delay. The R7284
operates an oil valve that prevents the flow of oil when
the burner motor is running prior to combustion (delayed
valve-on) and when the burner motor is running after
combustion (burner motor-off delay).
The R7284 models are intended for use only on oil
burning appliances which do not require prepurge and
post-purge as a safety related function as defined in
UL296. The valve-on delay and burner motor-off delay in
this control are intended only to help establish draft and
reduce oil after-drip related problems.
EnviraCOM™ enabled R7284's can be used with
EnviraLink® remote monitoring systems and hand-held
diagnostics. Use only R7284P and U models for
networking with other EnviraCOM™ enabled devices.
FEATURES
User Interface
There are two user interfaces: basic and advanced. Both
interfaces consist of three buttons: , , and "i."
INSTALLATION INSTRUCTIONS
The advanced interface has a two-line display used to
configure device parameters, retrieve diagnostic
information, and display system status.
The basic interface has a single LED used to display
error codes and system status.
In general, the "i" button cycles through the display
options and acts as an "enter" key (in setup modes).
Thermostat(s)
The oil primaries are compatible with both standard
thermostats and EnviraCOM™ communicating
thermostats.
Limited Recycle
This feature limits the number of recycle trials (for each
call for heat) to a maximum of three trials. If the flame is
lost three times and does not successfully satisfy a call
for heat, the R7284 locks out.
Pump Priming Cycle
To facilitate purging air from the oil lines and filters, the
R7284 can be placed in a purge routine by pressing and
releasing the up arrow button during the Trial For
Ignition.
In the advanced interface "PUMP PRIME" is displayed
on the display along with the time left on the Trial for
Ignition (TFI). Pressing the up arrow button adds a
minute to the TFI time for a maximum of 10 additional
minutes (press the up arrow button 10 times). Pressing
the down arrow button subtracts a minute from the TFI
time.
There is no visual indication for the basic interface
control and the purge timing is limited to five minutes.
Disable Function
Pressing and holding the "i" button will disable all control
functions until 3 seconds after the button is released.
Lockout Modes
The R7284 has three types of lockout modes that are
entered when an error is encountered:
69-2467EFS-05
Table des Matières
loading

Sommaire des Matières pour Honeywell EnviraCOM R7284B

  • Page 13: Caractéristiques

    Régulateur primaire à mazout électronique R7284B,P,U,G compatible EnviraCOM™ NOTICE D'INSTALLATION APPLICATION CARACTÉRISTIQUES Le régulateur à mazout électronique R7284B,P,U,G est Interface utilisateur un régulateur primaire à mazout à allumage intermittent et interrompu à tension secteur de sécurité pour les Il y a deux interfaces utilisateur : l'interface de base et brûleurs résidentiels à...
  • Page 14: Fonction De Désactivation

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Fonction de désactivation Minuterie : Temporisation d'ouverture de vanne : 0-30 secondes Le fait d'appuyer sur le bouton « i » sans relâcher permet Temporisation d'arrêt du brûleur : 0-8 minutes de désactiver toutes les fonctions du régulateur jusqu'à 3 secondes suivant le relâchement du bouton.
  • Page 15: Emplacement

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ INSTALLATION 1. Le câblage doit être conforme aux codes et aux règlements locaux. 2. Vérifier que le câblage de la tension secteur est bien connecté. Consulter l'étiquette du régulateur à Lors de l'installation de ce mazout et le schéma de câblage de l'appareil pour produit...
  • Page 16 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ R7284A, G R7284B, P, U VANNE VANNE VANNE MOTEUR DE MOTEUR DE MOTEUR DE MOTEUR DE BOUTON BRÛLEUR BRÛLEUR BRÛLEUR BRÛLEUR HAUT AFFICHEUR MF32180 BORNES DE BOUTON THERMOSTAT Fig. 5. Câblage du R7284 pour vanne à mazout en BOUTON i option.
  • Page 17 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ CONTRÔLEUR POMPE DE AQUASTAT® CIRCULATION L8148A,C R7284 THERMOSTAT LIMITEUR TH9421C VisionPRO IAQ CAVALIER CONTRÔLEUR AQUASTAT® BORNE ENVIRACOM™ MOTEUR DE L7224/48 MOTEUR DE R7284 BRÛLEUR BRÛLEUR LIMITEUR ALLUMEUR ALLUMEUR VANNE CELLULE DE CELLULE DE BORNE MOTEUR DE MOTEUR DE...
  • Page 18 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ IMPORTANT Le système montré à la Fig. 10 est sensible à la T8635L phase/polarité. S'assurer que toute la puissance C7089B CAPTEUR DE d'entrée est dans la même phase. TEMPÉRATURE EXTÉRIEURE W8635A RELAIS VENTI- LATEUR RELAIS...
  • Page 19: Interface Utilisateur Avancée

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ INTERFACE UTILISATEUR AVANCÉE HAUT/BAS ERREUR HISTORIQUE HAUT/BAS (NON SÉLECTIONNÉ) ÉCRAN D’ACCUEIL APPUYER SUR LES 3 BOUTONS (OUI SÉLECTIONNÉ) CELLULE CADMIUM (QUITTER SÉLECTIONNÉ) HISTORIQUE (SUITE SÉLECTIONNÉ) PÉRIOD ALLUMAGE ÉCRANS DE HISTORIQUE CONFIGURATION DE L’INSTALLATEUR COMPTAGE DE CYCLES MF32103A...
  • Page 20: Voir Historique

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Sélectionner entre anglais, français et REMARQUE : Le rétablissement des valeurs de espagnol en utilisant les boutons haut référence permet d'établir de nouvelles et bas et le bouton « i » pour valeurs de référence pour la cellule de sélectionner.
  • Page 21: Écrans D'historique Des Erreurs

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Statut R7284 (Interface de base) Le fait d'appuyer sur « i » au cours de tout écran de durée d'allumage permet de passer aux écrans de compte de cycle ci-dessous. Tableau 2. Codes DEL. Cycles totaux de brûleur.
  • Page 22: Étapes Préliminaires

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Codes d'erreur R7284 un appel de chaleur normal, une fois le régulateur en mode de fonctionnement, appuyer sur le bouton « i » et le (Interface de base) relâcher. Sur le modèle avancé, suivre la procédure de diagnostic à Tableau 4.
  • Page 23 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Tableau 5. Fonctionnement du R7284. Action externe R7284 Action Puissance appliquée au Vérification de sécurité interne effectuée. Si aucune lumière ou flamme n'est régulateur. détectée et que toutes les conditions internes sont correctes, le régulateur passe en mode de veille.
  • Page 24 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Tableau 6. Informations sur le dépannage. Condition : Le brûleur ne se lance pas avec l'appel de chaleur Procédure Statut du régulateur Action corrective Revoir l'historique des Consulter le tableau des codes d'erreur dans erreurs si le régulateur est cette section verrouillé...
  • Page 25 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Tableau 7. Informations sur les alarmes de l'affichage. PAS D'ALLUMAGE • La cellule de cadmium a détecté une certaine quantité de lumière VÉRIF. CELL CAD durant l'installation de l'essai d'allumage, mais pas suffisamment pour passer en mode de fonctionnement.
  • Page 26 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Tableau 7. Informations sur les alarmes de l'affichage. ERREUR ECOM • Une erreur de communication a été détectée. • Retirer tous les dispositifs des connexions EnviraCOM™, de la fiche à trois broches et des bornes à vis 1-2-3. —...
  • Page 27 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Tableau 8. Codes de clignotement DEL. Code cligno- Numéro tement d'alarme EnviraCOM™ Action corrective 10,5,20,59,9 Le brûleur n'était pas allumé ni allumé vers la fin de l'essai d'allumage. • Vérifier que le robinet manuel est ouvert. •...
  • Page 28 Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35, Dynamic Drive ® Marque de commerce déposée aux É.U. © 2011 Honeywell International Inc. Toronto (Ontario) M1V 4Z9 Tous droits réservés 69-2467EFS—05 M.S. Rev. 04-11 customer.honeywell.com...

Ce manuel est également adapté pour:

Enviracom r7284pEnviracom r7284uEnviracom r7284g

Table des Matières