7. Connect the power and outputs as shown in the Wiring Details.
8. Press the IAQPoint onto the plastic base (latches will click), making
certain that sampling tube feeds into the appropriate port on the
back of the IAQPoint.
Note: Honeywell uses ft/minute velocity rules, however other industries or
companies use CFM: To convert from CFM to velocity (ft/minute), divide
the flow by the area (Example: In a 2 ft x 4 ft duct, where the area is 8 sq.
ft with a CFM of 30,000, the air velocity will be 30,000 cu. ft/minute/(8 sq.
f
) = 3,750 ft/minute)
t
M-511703, Rev. 2
6/10
The IAQPoint with the temperature and humidity sensor
option must be duct mounted using a different method. See
following page for further details.