The transmitter can convert the input signal into a current or voltage
signal ("nominal output range"):
0 ... 5 V
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
The start value adjusted for the measuring range (see page 53) is rep-
resented by the lower limit of the nominal output range. The adjusted
end value is represented by the upper limit of the nominal output
range. Within the usable signal range (see table below), the input
value is correctly represented by the output signal.
When the output signal lies outside the usable signal range, the out-
put signal is set to an error value. This is signaled by the error LED.
Nominal
output range
0 ... 5 V
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
* for Model P 32000 P0/1x only:
A signal below the usable range is only recognized as error in the
4 ... 20 mA range
P 32000 P0/0x
Usable
signal range
0 ... 5.125 V
0 ... 10.25 V
0 ... 20.5 mA
3.8 ... 20.5 mA

Measuring Ranges

Model
P 32000 P0/1x
Usable
signal range*
0.1 ... 5.125 V
0.1 ... 10.25 V
3.8 ... 20.5 mA
3.8 ... 20.5 mA
Safe state
(error value)
≤ 0.1 V
≥ 5.25 V
≤ 0.1 V
≥ 10.5 V
≤ 3.6 mA
≥ 21 mA
≤ 3.6 mA
≥ 21 mA