The transmitter can convert the input signal into a current or voltage
signal ("nominal output range"):
0 ... 5 V
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
When the input signal lies outside the usable signal range, the output
signal is set to a substitute value. This is signaled by the error LED.
Nominal
output range
0 ... 5 V
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
* for Model P 32200 P0/1x only:
A signal below the usable range is only recognized as error in the
4 ... 20 mA range
P 32200 P0/0x
Usable
signal range
0 ... 5.125 V
0 ... 10.25 V
0 ... 20.5 mA
3.8 ... 20.5 mA
Measuring Ranges
Model
P 32200 P0/1x
Usable
signal range*
0.1 ... 5.125 V
0.1 ... 10.25 V
3.8 ... 20.5 mA
3.8 ... 20.5 mA
Safe state
(error value)
≤ 0.1 V
≥ 5.25 V
≤ 0.1 V
≥ 10.5 V
≤ 3.6 mA
≥ 21 mA
≤ 3.6 mA
≥ 21 mA
37