ThermoTrans®
Stratos Pro A2... pH
deutsch
P32100P0/11-S0002-KTA
Betriebsanleitung
The Art of Measuring.
A2... PH
3
35
67
BVS 10 ATEX E089 X
II 1G Ex ia IIC T3/T4/T6
14163 Berlin
SE 706X/1-NMSN
BVS 10 ATEX E089 X
II 1G Ex ia IIC T3/T4/T
14163 Berlin
SE 706X/2-NMSN
BVS 10 ATEX E089 X
II 1G Ex ia IIC T3/T4/T
www.knick.de
14163 Berlin
SE 706X/2-NM
14163 Berlin
BVS 10 ATEX E
SE 706X/1-NM
II 1G Ex ia IIC
BVS 10 ATEX
II 1G Ex ia IIC
14163 Berlin
SE 706X/2-NM
BVS 10 ATEX
II 1G Ex ia IIC

Publicité

Table des Matières
loading

Sommaire des Matières pour Knick ThermoTrans P32100P0/11-S0002-KTA

  • Page 1 Temperatur-Meßumformer ..Instructions for Use Temperature Transmitters..Mode d‘emploi Convertisseurs de température ..www.knick.de Aktuelle Produktinformation: Aktuelle Produktinformation: www.knick.de...
  • Page 3 T her mo T r a ns Temperature Transmitter Power P32100P0/11-S0002-KTA T ype 0785470000000 ES03 Operat. T emp. 0 to +55 (65) °C DIP S1 = On www.knick.de Made in Germany SIL2 Functional Safety Type Approved ® Rheinland T Ü V www.knick.de...
  • Page 4 Garantie Garantie Innerhalb von 5 Jahren ab Lieferung auftretende Mängel werden bei freier Anlieferung im Werk kostenlos behoben. Zubehör: 1 Jahr. Änderungen vorbehalten. Rücksendung Kontaktieren Sie das Service-Team, Kontaktdaten siehe Rückseite. Senden Sie das Gerät gereinigt an die Ihnen genannte Adresse. Entsorgung Die landesspezifischen gesetzlichen Vorschriften für die Entsorgung von “Elektro/Elektronik-Altgeräten”...
  • Page 5: Table Des Matières

    Inhaltsverzeichnis Garantie .................... 4 Sicherheitshinweise ............... 7 Bestimmungsgemäßer Gebrauch ..........8 Prinzipschaltbild ................... 8 Funktion ................... 9 3-Port-Trennung der Eingänge, Ausgänge und Stromversorgung ................. 9 Montage und elektrischer Anschluß ........10 Maßzeichnung und Schaltelemente ..........10 Meßbereiche .................11 Ausgangs nennbereich ..............11 Verhalten des Ausgangsstroms (4 ... 20 mA) bei Meßbereichsüber- bzw.
  • Page 6 Inhaltsverzeichnis Technische Daten .................23 Eingangsdaten Widerstandsthermometer / Widerstand (RTD / R) ................23 Eingangsdaten Thermoelemente (TC) ........24 Ausgangsdaten ...................25 Übertragungsverhalten ..............26 Hilfsenergie ..................26 Isolation ....................26 Normen und Zulassungen ..............27 weitere Daten ..................28 Bestelldaten ...................29...
  • Page 7: Sicherheitshinweise

    Sicherheitshinweise Warnung! Schutz gegen gefährliche Körperströme Bei Anwendungen mit hohen Arbeitsspannungen ist auf genügend Abstand bzw. Isolation zu Nebengeräten und auf Berührungsschutz zu achten. Achtung! Beim Umgang mit den Bausteinen ist auf Schutzmaßnah- men gegen elektrostatische Entladung (ESD) zu achten. Achtung! P 32100P0/11-S0002 Die Universal-Meßumformer PolyTrans®...
  • Page 8: Bestimmungsgemäßer Gebrauch

    Bestimmungsgemäßer Gebrauch Die Temperatur-Meßumformer ThermoTrans® P 32100P0/11-S0002- KTA bieten Anschlußmöglichkeiten für alle gängigen Thermoelemente und Widerstandsmeßfühler sowie Kombifühler. Bei Widerstandsmeßfühlern wird die Anschlußkonfiguration 2-, 3- oder 4-Leiterschaltung beim Gerätestart automatisch erkannt. Das Ausgangssignal ist einstellbar auf 0 / 4 ... 20 mA oder 0 ... 5 / 10 V. Die Umschaltung der Meßbereiche erfolgt kalibriert über DIP- und Drehcodierschalter.
  • Page 9: Funktion

    Funktion Der Temperatur-Meßumformer tastet Signale von Thermoelementen,bzw. Widerstandsmeßfühlern periodisch ab und formt den Abtastwert in ein dem Meßwert proportionales Ausgangssi- gnal um. Das Ausgangssignal kann als Spannungs- oder Stromsignal ausgege- ben werden. Eine 3-Port-Trennung mit sicherer Trennung nach EN 61140 bis zu 300 VAC/DC garantiert Personen- und Anlagenschutz sowie eine unverfälschte Übertragung der Meßsignale.
  • Page 10: Montage Und Elektrischer Anschluß

    Montage und elektrischer Anschluß Die Meßumformer werden auf TS 35 Normschienen aufgerastet und seitlich durch geeignete Endwinkel fixiert. Klemmenbelegung siehe Maßzeichnung. Anschlußquerschnitt: 0,2 mm ... 2,5 mm (AWG 24-14). Maßzeichnung und Schaltelemente Bedienöffnung für Taster Betriebs-LED (grün) Status-LED (gelb) Melde-LED (rot) Taster Eingang 1 + Startwert (2 Drehcodierschalter)
  • Page 11: Meßbereiche

    Meßbereiche Der Meßumformer kann das Eingangssignal in ein Strom- oder Span- nungssignal umwandeln („Ausgangsnennbereich“): 0 ... 5 V 0 ... 10 V 0 ... 20 mA 4 ... 20 mA Dabei wird der eingestellte Start-Wert des Meßbereichs (siehe S. 18) auf den Anfang des Ausgangsnennbereichs und der End-Wert auf das Ende des Ausgangsnennbereichs abgebildet.
  • Page 12: Verhalten Des Ausgangsstroms (4

    Meßbereiche Verhalten des Ausgangsstroms (4 ... 20 mA) bei Meßbereichsüber- bzw. -unterschreitung...
  • Page 13: Beschaltungsvarianten (Sensoranschluß)

    Beschaltungsvarianten (Sensoranschluß) ThermoTrans P32100P0/11-S0002-KTA Einstellbar über: Sensor Anschluß Abbildung IrDA Schal- 0 ... 5kOhm 2-, 3- oder 4-Leiter, 1, 2, 3 oder fest eingestellt 5 .. 100 kOhm 0 ... 5kOhm 2-, 3- oder 4-Leiter, 1, 2, 3 oder automatische Erkennung 5 ..
  • Page 14 Beschaltungsvarianten Anschluß von Widerstandsthermometern / Widerstandsgebern RTD / Widerstand RTD / Widerstand RTD / Widerstand 4-Leiter 3-Leiter 2-Leiter: (bei 2-Leiter- Messung mit R > 5kΩ ist eine Brücke zwischen Klemme 1 und Klemme 2 zu setzen) nur über IrDA Mit Hilfe der Software Paraly 111 kann der volle Funktionsumfang des Meßumformers parametriert wer- den.
  • Page 15 Beschaltungsvarianten Anschluß von Widerstandsthermometern / Thermoelementen RTD Differenz: Differenz Diff Diff Ext. Kaltstellen- TC Summen- kompensation schaltung Pt 100 Mit Hilfe der Software Paraly 111 kann der volle Funktionsumfang des Meßumformers parametriert wer- den. Beschaltungsbeispiele mit grau hinterlegter Abbildungsnummer sind nur über IrDA einstellbar.
  • Page 16: Anschluß Kombifühler

    Beschaltungsvarianten Anschluß Kombifühler Kombifühler Mit Hilfe der Software Paraly 111 kann der volle Funktionsumfang des Meßumformers parametriert wer- den. Beschaltungsbeispiele mit grau hinterlegter Abbildungsnummer sind nur über IrDA einstellbar.
  • Page 17: Anschluß Thermoelement (Summenschaltung)

    Beschaltungsvarianten Anschluß Thermoelement (Summenschaltung) TC Summenschaltung Hinweis: In Summenschaltung können maximal 10 Thermoelemente ange- schlossen werden. Mit Hilfe der Software Paraly 111 kann der volle Funktionsumfang des Meßumformers parametriert wer- den. Beschaltungsbeispiele mit grau hinterlegter Abbildungsnummer sind nur über IrDA einstellbar.
  • Page 18: Konfigurierung Über Schalter

    Konfigurierung über Schalter Stellen Sie die DIP- und Drehcodierschalter gemäß Tabelle (Gehäuse- aufdruck) ein. Sensortyp: Angeschlossenen Sensor über Schalter DIP1 bis DIP3 einstellen. Startwert: Stellen Sie den Ziffernwert (00 ... 99) mit Hilfe der Drehkodierschalter „Start“ ein. Über die Schalter DIP4, DIP5 stellen Sie den Faktor ein. Eine fallende Kennlinie wird durch die Einstellung Startwert größer Endwert realisiert.
  • Page 19: Kommunikation Über Irda-Schnittstelle

    Parameter des Meßumformers (siehe Tabelle auf Seite 13). Die Softwa- re wird mit einer detaillierten Anleitung ausgeliefert, welche auch als Download auf der Website „www.knick.de“ zur Verfügung steht. Erweiterte Funktionsmerkmale des Universal-Meßumformers durch Kommunikation über die Software „Paraly SW 111“:...
  • Page 20: Konfigurierung Über Schalter: Funktionsübersicht

    Konfigurierung über Schalter: Funktionsübersicht = DIP-Schalter ON...
  • Page 21: Konfigurierung Über Schalter: Beispiel

    Konfigurierung über Schalter: Beispiel Sensor: Thermoelement Typ J Meßbereich: 200 ... 1200 °C Ausgangssignal: 4 - 20 mA 1. Sensortyp einstellen: TC Typ J: DIP1 = 1, DIP2 = 0, DIP 3 = 1 2. Startwert einstellen: 200 °C Dieser Startwert setzt sich zusammen: Ziffernwert = 20, Faktor = x10. Ziffernwert mit Drehkodierschaltern einstellen: Dazu Faktor x10 einstellen: DIP4 = 0, DIP5 = 1...
  • Page 22: Led Und Fehlersignalisierung Am Gerät

    LED und Fehlersignalisierung am Gerät Hinweis: Grüne und rote LED blinken beim Gerätestart kurz auf. grün: Versorgungsspannung vorhanden gelb: Beim Start einmalige Signalisierung der erkannten Anschlußart bei RTD-Messung (2-/3-/4-maliges Blinken entspricht 2-/3-/4-Leitermessung) Blinken: IrDA aktiv Dauerlicht: IrDA verbunden rot: Fehlerstatus; die LED blinkt mit der Anzahl der Fehlernummer Ausgang [mA] Ausgang [V] Nr.
  • Page 23: Technische Daten

    Technische Daten Eingangsdaten Widerstandsthermometer / Widerstand (RTD / R) Gebertyp (Norm) Meßbereich [°C] Pt100 (DIN 60751) - 200 ... 850 Pt200 (DIN 60751) - 200 ... 850 Pt300 (DIN 60751) - 200 ... 850 Pt1000 (DIN 60751) - 200 ... 850 Ptxxx (DIN 60751) - 200 ...
  • Page 24: Eingangsdaten Thermoelemente (Tc)

    Technische Daten Eingangsdaten Thermoelemente (TC) Gebertyp (Norm) Meßbereich [°C] nur über IrDA wählbar (DIN 60584-1) 250 ... 1820 (DIN 60584-1) - 200 ... 1000 (DIN 60584-1) - 210 ... 1200 (DIN 60584-1) - 200 ... 1372 (DIN 43710) - 200 ... 900 (DIN 60584-1) - 200 ...
  • Page 25: Ausgangsdaten

    Technische Daten Ausgangsdaten Ausgänge 0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V oder 0 ... 5 V, kalibriert umschaltbar Aussteuerbereich 0 % bis ca. 102,5 % der Meßspanne bei 0 ... 20 mA, 0 ... 10 V bzw. 0 ...
  • Page 26: Übertragungsverhalten

    Technische Daten Übertragungsverhalten Kennlinie Linear steigend / fallend; über IrDA: parametrierbare Kennlinie mit Stütz- stellen oder über Polynome Meßrate ca. 3 / s ca. 2 / s im Betriebsmodus Thermoelement mit ext. Vergleichs- stellenkompensation bzw. Widerstandsmessung 5 k ... 100 kOhm Einstellzeit t 99* 300 ms 500 ms im Betriebsmodus Thermoelement mit ext.
  • Page 27: Normen Und Zulassungen

    Technische Daten Schutz gegen gefährliche Sichere Trennung nach DIN EN 61140 (VDE 0140 Teil 1) durch verstärkte Isolie- Körperströme rung gemäß DIN EN 61010-1 (VDE 0411 Teil 1). Arbeitsspannung bis zu 300 V AC/ DC bei Überspannungskategorie II und Verschmutzungsgrad 2 zwischen allen Kreisen.
  • Page 28: Weitere Daten

    Technische Daten weitere Daten Umgebungstemperatur bei Betrieb 0 ... + 65 °C Einzelgerät mit Abstand > 6 mm zu Nachbargeräten 0 ... + 55 °C (angereihter Zustand; Die Geräte werden unter Verwendung der Zwischenstücke ZU0784 montiert) bei Lagerung - 25 ... + 85 °C Umgebungsbedingungen Ortsfester Einsatz, wettergeschützt rel.
  • Page 29: Bestelldaten

    Bestelldaten Bestellnr. Universal-Meßumformer, einstellbar P32100P0/11-S0002-KTA Zubehör Bestellnr. Kommunikations-Software Paraly ® SW 111 SW111...
  • Page 35 T her mo T r a ns Temperature Transmitter Power P32100P0/11-S0002-KTA T ype 0785470000000 ES03 Operat. T emp. 0 to +55 (65) °C DIP S1 = On www.knick.de Made in Germany SIL2 Functional Safety Type Approved ® Rheinland T Ü V www.knick.de...
  • Page 36 Warranty Warranty Defects occurring within 5 years from delivery date shall be remedied free of charge at our plant (carriage and insurance paid by sender). Accessories: 1 year. Subject to change without notice. Return of products Please contact our Service Team before returning a defective device (see back cover for contact details).
  • Page 37 Table of Contents Warranty ..................36 Safety Information ...............39 Intended Use .................40 Block diagram ..................40 Function ..................41 3-port isolation of inputs, outputs and power supply ..41 Mounting and Electrical Connection ........42 Dimension drawing and control elements.......42 Measuring Ranges ................43 Nominal output range ..............43 Response of output current (4 ...
  • Page 38 Table of Contents Specifications ................55 Input data for resistance thermometer / resistor (RTD / R) .................55 Input data for thermocouple (TC) ..........56 Output data..................57 Response ....................58 Power supply ..................58 Isolation ....................58 Standards and approvals ..............59 Other data ....................60 Order Information ................61...
  • Page 39: Safety Information

    Safety Information Warning! Protection against electric shock For applications with high working voltages, ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks. Caution! Be sure to take protective measures against electrostatic discharge (ESD) when handling the devices! Caution! P32100P0/11-S0002-KTA The PolyTrans®...
  • Page 40: Intended Use

    Intended Use The ThermoTrans® P 32100P0/11-S0002-KTA temperature trans mitters provide connection possibilities all common thermocouples and resistance thermometers. When a resistive sensor is connected, 2-, 3-, or 4-wire configuration is automatically recognized at device startup. The output signal is adjustable to 0 / 4 ... 20 mA, or 0 … 5 / 10 V. The calibrated range selection is performed using DIP and rotary coding switches.
  • Page 41: Function

    Function The temperature transmitter periodically samples signals from thermo couples or resistance thermometers. These signals are converted into output signals proportional to the measured values. The output signal can be a voltage or a current. 3-port isolation with Safe Isolation up to 300 V AC/DC according to EN 61140 ensures optimum protection of personnel and equipment as well as unaltered transmission of measuring signals.
  • Page 42: Mounting And Electrical Connection

    Mounting and Electrical Connection The transmitters are snapped onto TS 35 standard rails and laterally fixed by suitable end brackets. See dimension drawing for terminal as- signments. Conductor cross-section: 0.2 mm ... 2.5 mm (AWG 24-14). Dimension drawing and control elements Hole for pushbutton Operation LED (green) Status LED (yellow)
  • Page 43: Measuring Ranges

    Measuring Ranges The transmitter can convert the input signal into a current or voltage signal ("nominal output range"): 0 ... 5 V 0 ... 10 V 0 ... 20 mA 4 ... 20 mA The start value adjusted for the measuring range (see Pg 50) is repre- sented by the lower limit of the nominal output range.
  • Page 44: Response Of Output Current (4

    Measuring Ranges Response of output current (4 ... 20 mA) to out-of-range conditions 21.0 20.5 Input Start value End value...
  • Page 45: Wiring Possibilities (Sensor Connection)

    Wiring Possibilities (Sensor Connection) ThermoTrans P32100P0/11-S0002-KTA Adjustable via: Sensor Type Connection Figure IrDA Switch 0 ... 5kohms 2-, 3- or 4-wire, 1, 2, 3 fixed setting 5 ... 100 kohms 0 ... 5kohms 2-, 3- or 4-wire, 1, 2, 3 automatic recognition 5 ...
  • Page 46 Wiring Possibilities Connection of resistance thermometers / resistance transducers RTD / Resistor RTD / Resistor RTD / Resistor 4-wire 3-wire 2-wire: (For 2-wire measure- ment with R > 5kΩ, place jumper across ter- minal 1 and terminal 2) via IrDA only You can configure all functions of the transmitter using the Paraly SW 111 software.
  • Page 47 Wiring Possibilities Connection of resistance thermometers / thermocouples RTD difference: difference: Diff Diff Ext. cold junction TC summing compensation configuration Pt 100 You can configure all functions of the transmitter using the Paraly SW 111 software. Wirings with a shaded number can only be adjusted via IrDA.
  • Page 48: Connection Of Combo Probe

    Wiring Possibilities Connection of combo probe Combo probe You can configure all functions of the transmitter using the Paraly SW 111 software. Wirings with a shaded number can only be adjusted via IrDA.
  • Page 49: Connection Of Thermocouple (Summing Configuration)

    Wiring Possibilities Connection of thermocouple (summing configuration) TC summing configuration Please note: You can only connect up to 10 thermocouples in summing configuration. You can configure all functions of the transmitter using the Paraly SW 111 software. Wirings with a shaded number can only be adjusted via IrDA.
  • Page 50: Configuration Using Switches

    Configuration using Switches Adjust the DIP and rotary switches according to the table on the housing. Sensor type: Select the connected sensor type using switches DIP1 to DIP3. Start value: Adjust the number (00 ... 99) using the "Start“ rotary switches. Adjust the factor using the switches DIP4, DIP5.
  • Page 51: Communication Via Irda Interface

    PC or PDA. It allows configuring all transmitter parameters (see table on Pg 45). The software comes with detailed instructions which are also available for download at "www.knick.de". Additional functions of the temperature transmitter when using "Paraly SW 111" software:...
  • Page 52: Configuration Using Switches: Overview Of Functions

    Configuration using Switches: Overview of Functions = DIP switch ON...
  • Page 53: Configuration Using Switches: Example

    Configuration using Switches: Example Sensor: Thermocouple type J Range: 200 ... 1200 °C Output signal: 4 - 20 mA 1. Adjust sensor type: TC Type J: DIP1 = 1, DIP2 = 0, DIP 3 = 1 2. Adjust start value: 200 °C This start value is composed of: numerical value = 20, factor = x10.
  • Page 54: Leds And Error Signaling On Device

    LEDs and Error Signaling on Device Note: Green and red LEDs flash momentarily at device startup. Green: Supply voltage provided Yellow: For RTD measurement, the identified connection type is signaled once at the start (2/3/4-time blinking corresponds to 2/3/4-wire measurement) Blinking: IrDA active Constant light: IrDA connected...
  • Page 55: Specifications

    Specifications Input data for resistance thermometer / resistor (RTD / R) Sensor type (Standard) Range [°C] Pt100 (DIN 60751) -200 ... 850 Pt200 (DIN 60751) -200 ... 850 Pt300 (DIN 60751) -200 ... 850 Pt1000 (DIN 60751) -200 ... 850 Ptxxx (DIN 60751) -200 ...
  • Page 56: Input Data For Thermocouple (Tc)

    Specifications Input data for thermocouple (TC) Sensor (Standard) Range [°C] Selectable via type IrDA only (DIN 60584-1) 250 ... 1820 (DIN 60584-1) -200 ... 1000 (DIN 60584-1) -210 ... 1200 (DIN 60584-1) -200 ... 1372 (DIN 43710) -200 ... 900 (DIN 60584-1) -200 ...
  • Page 57: Output Data

    Specifications Output data Outputs 0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V or 0 ... 5 V, Calibrated switching Control range 0% to approx. 102.5% span for 0 ... 20 mA, 0 ... 10 V or 0 ...
  • Page 58: Response

    Specifications Response Characteristic Rising / falling linearly; via IrDA: curve defined by sampling points or polynomials Measuring rate Approx. 3 / s Approx. 2 / s in operating mode: thermocouple with ext. reference junction compensation or resistance measurement 5 k ... 100 kohms Response time t 99* 300 ms 500 ms in operating mode:...
  • Page 59: Standards And Approvals

    Specifications Protection against Safe Isolation to EN 61140 by reinforced insulation according to EN 61010-1. electric shock Working voltage up to 300 V AC/DC across all circuits with overvoltage category II and pollution degree 2. For applications with high working volt- ages, ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks.
  • Page 60: Other Data

    Specifications Other data Ambient temperature during operation 0 ... +65 °C single unit with > 6 mm spacing to adjacent devices 0 ... +55 °C (mounted in row) The devices are mounted using ZU0784 spacers) during storage -25 ... 85 °C Ambient conditions Stationary application, weather-protected Relative air humidity 5 ...
  • Page 61: Order Information

    Order Information Type Order No.: Temperature transmitters, adjustable P32100P0/11-S0002-KTA Accessories Order No.: Paraly® SW 111 communication software SW111...
  • Page 67 T her mo T r a ns Temperature Transmitter Power P32100P0/11-S0002-KTA T ype 0785470000000 ES03 Operat. T emp. 0 to +55 (65) °C DIP S1 = On www.knick.de Made in Germany SIL2 Functional Safety Type Approved ® Rheinland T Ü V www.knick.de...
  • Page 68 Garantie Garantie Tout défaut constaté dans les 5 ans à dater de la livraison sera réparé gratuitement à réception franco de l'appareil. Accessoires : 1 an. Sous réserve de modifications. Retour Contactez le service après-vente, les coordonnées se trouvent au dos. Envoyez l'appareil après l'avoir nettoyé...
  • Page 69 Table des matières Garantie ......................68 Consignes de sécurité ..................71 Utilisation conforme ..................72 Schéma de principe ....................72 Fonction ......................73 Isolation 3 ports des entrées, des sorties et de l'alimentation ....73 Montage et raccordement électrique ............74 Dessin coté et éléments de commande ............74 Plages de mesure .....................
  • Page 70 Table des matières Caractéristiques techniques ................87 Données d'entrée Thermomètre à résistance / Résistance (RTD / R) ....................87 Données d'entrée Thermocouples (TC) ............88 Données de sortie ....................89 Caractéristique de transmission .................90 Alimentation auxiliaire ...................90 Isolation ........................90 Normes et homologations ...................91 Autres caractéristiques ..................92 Références......................
  • Page 71: Consignes De Sécurité

    Consignes de sécurité Avertissement ! Protection contre les chocs électriques En cas d’utilisation avec des tensions de service élevées, veiller à avoir une distance ou une isolation suffisante par rapport aux appareils voisins et respecter la protection aux contacts. Attention ! Lors de la manipulation des composants, appliquer des mesures de protection contre les décharges électrostatiques (ESD).
  • Page 72: Utilisation Conforme

    Utilisation conforme Les convertisseurs de température ThermoTrans® P 32100P0/11-S0002-KTA offrent des possibilités de raccordement pour la plupart des thermocouples et sondes résistives ainsi que pour les sondes combinées. Pour les sondes résistives, la configuration de raccordement 2, 3 ou 4 fils est détectée automatiquement au démarrage de l'appareil.
  • Page 73: Fonction

    Fonction Le convertisseur de température balaie régulièrement les signaux des thermocouples ou des sondes résistives et convertit la valeur balayée en un signal de sortie proportionnel à la valeur de mesure. Le signal de sortie peut être émis sous forme de signal de tension ou sous forme de signal de courant.
  • Page 74: Montage Et Raccordement Électrique

    Montage et raccordement électrique Les convertisseurs sont clipsés sur les rails normalisés TS 35 et fixés latérale- ment par une équerre d'embout appropriée. Pour le brochage, voir le dessin coté. Section de raccordement : 0,2 mm ... 2,5 mm (AWG 24-14). Dessin coté...
  • Page 75: Plages De Mesure

    Plages de mesure Le convertisseur peut convertir le signal d'entrée en un signal de courant ou de tension (“plage nominale de sortie”) : 0 ... 5 V 0 ... 10 V 0 ... 20 mA 4 ... 20 mA La valeur initiale de la plage de mesure réglée (cf. p. 82) est alors représentée au début de la plage nominale de sortie et la valeur finale est représentée à...
  • Page 76: Comportement Du Courant De Sortie (4

    Plages de mesure Comportement du courant de sortie (4 ... 20 mA) en cas de dépassement positif ou négatif de la plage de mesure 21,0 20,5 Entrée Valeur initiale Valeur finale...
  • Page 77: Variantes De Connexion (Raccordement Du Capteur)

    Variantes de connexion (raccordement du capteur) ThermoTrans P32100P0/11-S0002-KTA Réglage : Capteur Type Raccord Figure IrDA Com- muta- teur 0 ... 5kΩ 2, 3 ou 4 fils, 1, 2, 3 réglage fixe 5 ... 100 kΩ 0 ... 5kΩ 2, 3 ou 4 fils, 1, 2, 3 détection automatique...
  • Page 78 Variantes de connexion Raccordement des thermomètres à résistance et des convertisseurs à résistance RTD / Résistance RTD / Résistance RTD / Résistance 4 fils 3 fils 2 fils : (pour une mesure à 2 fils avec R > 5kΩ il faut placer un pont entre la borne 1 et la borne 2) uniquement via l'IrDA...
  • Page 79 Variantes de connexion Raccordement des thermomètres à résistance et des thermocouples Différence TC : Différence RTD : Diff Diff Compensation de soudure froide ext. Circuit de connexion Pt 100 additionneur Il est possible de programmer toutes les fonctions du convertisseur à l'aide du logiciel Paraly 111. Les exemples de connexion pourvus d'un numéro de figure grisé...
  • Page 80: Raccordement Sonde Combinée

    Variantes de connexion Raccordement sonde combinée Sonde combinée Il est possible de programmer toutes les fonctions du convertisseur à l'aide du logiciel Paraly 111. Les exemples de connexion pourvus d'un numéro de figure grisé ne peuvent être programmés qu'avec l'IrDA.
  • Page 81: Raccordement Du Thermocouple (Circuit De Connexion Additionneur)

    Variantes de connexion Raccordement du thermocouple (circuit de connexion additionneur) Circuit de connexion additionneur Remarque : Dans un circuit de connexion additionneur, 10 thermocouples peuvent être raccordés au maximum Il est possible de programmer toutes les fonctions du convertisseur à l'aide du logiciel Paraly 111. Les exemples de connexion pourvus d'un numéro de figure grisé...
  • Page 82: Configuration Via Les Commutateurs

    Configuration via les commutateurs Réglez les commutateurs DIP et les commutateurs rotatifs selon le tableau marqué sur le boîtier. Type de capteur : Régler le capteur raccordé avec les commutateurs DIP1 à DIP3. Valeur initiale : Programmez la valeur chiffrée (00 à 99) à l'aide des commutateurs rotatifs “Start”.
  • Page 83: Communication Via L'interface Irda

    (cf. tableau sur la page 77). Le logiciel est livré avec une notice d'utilisation détaillée, qui peut aussi être téléchargée sur le site Internet “www.knick.de”. Caractéristiques de fonctionnement étendues du convertisseur de température par communication avec le logiciel “Paraly SW 111”...
  • Page 84: Configuration Via Les Commutateurs

    Configuration via les commutateurs : aperçu des fonctions = Commutateur DIP ON...
  • Page 85: Configuration Via Les Commutateurs : Exemple

    Configuration via les commutateurs : exemple Capteur : Thermocouple type J Plage de mesure : 200 ... 1200 °C Signal de sortie : 4 ... 20 mA 1. Régler le type de capteur : TC type J : DIP1 = 1, DIP2 = 0, DIP 3 = 0 2.
  • Page 86: Led Et Signalisation Des Erreurs Sur L'appareil

    LED et signalisation des erreurs sur l'appareil Remarque : Les LED rouge et verte clignotent brièvement au démarrage de l'appareil. vert : tension d'alimentation présente jaune : au démarrage, une seule indication du type de raccordement détecté pour la mesure RTD (un clignotement répété...
  • Page 87: Caractéristiques Techniques

    Caractéristiques techniques Données d'entrée Thermomètre à résistance / Résistance (RTD / R) Type de (Norme) Plage de mesure [°C] capteur Pt100 (DIN 60751) - 200 ... 850 Pt200 (DIN 60751) - 200 ... 850 Pt300 (DIN 60751) - 200 ... 850 Pt1000 (DIN 60751) - 200 ...
  • Page 88: Données D'entrée Thermocouples (Tc)

    Caractéristiques techniques Données d'entrée Thermocouples (TC) Type de (Norme) Plage de mesure [°C] sélectionnable capteur uniquement via l'IrDA (DIN 60584-1) 250 ... 1820 (DIN 60584-1) - 200 ... 1000 (DIN 60584-1) - 210 ... 1200 (DIN 60584-1) - 200 ... 1372 (DIN 43710) - 200 ...
  • Page 89: Données De Sortie

    Caractéristiques techniques Données de sortie Sorties 0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V ou 0 ... 5 V, calibrée commutable Plage utile 0 % jusqu'à env. 102,5 % de la fourchette pour 0 ... 20 mA, 0 ... 10 V ou 0 ...
  • Page 90: Caractéristique De Transmission

    Caractéristiques techniques Caractéristique de transmission Courbe caractéristique Linéaire montante/descendante ; via IrDA : paramétrable avec points d'appui par IrDA ou par polynôme Cadence de mesure env. 3 / s env. 2 / s dans le mode de fonctionne- ment : thermocouple avec compensa- tion externe des points de comparaison mesure de résistance 5 k ... 100 kΩ...
  • Page 91: Normes Et Homologations

    Caractéristiques techniques Protection contre les Séparation sûre suivant EN 61140 par chocs électriques isolation renforcée suivant EN 61010-1. Tension de service jusqu'à 300 V CA/ CC pour la catégorie de surtension II et le degré de pollution 2 entre tous les circuits.
  • Page 92: Autres Caractéristiques

    Caractéristiques techniques Autres caractéristiques Température ambiante en fonctionnement 0 ... + 65 °C (chaque appareil distant de > 6 mm des appareils voisins) 0 ... + 55 °C (disposition en série ; Les appareils sont montés à l'aide des raccords ZU0784) en stockage - 25 ... + 85 °C Conditions environnantes Utilisation fixe sur site, à...
  • Page 93: Références

    Références Type N° de cde Convertisseur de température réglable P32100P0/11-S0002-KTA Accessoires N° de cde Logiciel de communication Paraly ® SW 111 SW111...