Input data for resistance thermometer / resistor (RTD / R)

Sensor type (Standard)
Pt100
(DIN 60751)
Pt200
(DIN 60751)
Pt300
(DIN 60751)
Pt1000
(DIN 60751)
Ptxxx
(DIN 60751)
Pt100-TC combo probe
Type K
Ni100
(DIN 43760)
Nixxx
(DIN 43760)
Connection
Resistance range
(incl. line resistance)
Max. line resistance
Supply current
Line monitoring
Input error limits
Temperature coefficient
at input
Range [°C]
-200 ... 850
-200 ... 850
-200 ... 850
-200 ... 850
-200 ... 850
-200 ... 850 (Model C73458-A28-B101)
- 60 ... 180
- 60 ... 180
2-, 3- or 4-wire
(automatic identification)
Temperature measurement: 0 ... 5 kΩ
Resistance measurement: 0 ... 5 kΩ
or 5 ... 100 kΩ
100 Ω
Max. 500 µA
Open circuits
For resistances < 5 kΩ:
± (50 mΩ + 0.05% meas.val.)
for spans > 15 Ω
For resistances > 5 kΩ:
± (1 Ω + 0.2% meas.val.)
for spans > 50 Ω
50 ppm/K of adjusted end value
(average TC in permitted operating
temp range, reference temp 23 °C)