Warning!
Protection against electric shock
For applications with high working voltages, ensure there
is sufficient spacing or isolation from neighboring devices
and protection against electric shocks.
Caution!
Be sure to take protective measures against electrostatic
discharge (ESD) when handling the devices!
Caution!
P32100P0/11-S0002-KTA
The PolyTrans®
installed only by qualified and specially trained personnel authorized by the
operating company. Do not connect the device to power supply before it is
professionally installed. Do not change the measuring range during opera-
tion. Observe the national codes and regulations during installation and
selection of cables and lines.
• Connecting cables must have a temperature rating of ≥ 80 °C.
• Mains supply must be protected by a fuse ≤ 20 A.
• Warning against misuse: Do not operate the device outside the conditions
specified by the manufacturer, as this might result in hazards to operators
or malfunction of the equipment. The system installer is responsible for
the safety of the system in which the device is integrated.
Prior to commissioning and after each change of the configuration, you
must check the intended function of the transmitter (see Safety Manual, sec-
tion 5.1 "Functional Checks").
Safety precautions for supply voltages of
55 VAC / 140 VDC and above
• The device must be installed in a tool-secured enclosure.
• Be sure to install a two-pole circuit breaker between device
and mains supply. It must be clearly identifiable and easily
accessible by the operator.