Generally there are two possible types of GSD using profile 3.0:
• Manufacturers specific GSD: With this GSD, unlimited functionality of the field unit is guaran-
teed. Unit-specific process parameters and functions are therefore available.
• Profile GSD: Differentiates itself in the number of the AI (analogue input) blocks and the measu-
rement principles. As long as a plant has been planned using the profile GSD's, an exchange of
units from different manufacturers can be made.
Note!
Before planning it must be decided with which GSD the plant is to be operated. It is possible to
change this setting using a class 2 master.
Factory default set-up: Manufacturer specific GSD.
The TMT184 temperature head transmitter supports the GSD's with the ident numbers in the fol-
lowing table:
Unit name
Manufacturer spec.
ID-no.
TMT184
1523 (Hex)
®
PROFIBUS-PA
(IEC 61158-2)
Profile 3.0 GSD
PA039700.gsd
Each unit receives an identification number (ID-no.) from the Profibus users organisation (PNO).
From this, the name of the Device Data Base (GSD) is formed. For Endress+Hauser this ID no. starts
with the manufacturer's identification 15xx. In order to gain a better allocation and individuality to
the respective GSD, the GSD names (without the type files) at Endress+Hauser are as follows:
• EH3_15xx:
EH= Endress+Hauser,
3= Profile 3.0,
_= Standard identification and
15xx= ID-no.
• EH3x15xx:
EH= Endress+Hauser,
3 = Profile 3.0,
x = Expanded identification and
15xx= ID-no.
The GSD files of all Endress+Hauser files can be requested under:
• Internet: Endress+Hauser
www.endress.com → (Products → Process Solutions → PROFIBUS → GSD files)
• Internet: PNO
www.profibus.com (GSD library)
• On CD ROM from Endress+Hauser: Order number 50097200
Content structure of the Endress+Hauser GSD files
For the Endress+Hauser field transmitters using the PROFIBUS interface all data required for pro-
jecting is contained in one file. After unpacking, this file is created using the following structure:
The identification revision #xx stands for a specific unit version. In the directory BMP unit specific
bitmaps can be found, these can be used independently from the projecting software.
The GSD files are saved in the GSD folder in the subdirectories extended and standard. Information
for using the field transmitter and the dependency in the unit software is stored in the folder Info.
Profile 3.0 ID-no.
9700 (Hex)
EH3_1523.gsd
EH3X1523.gsd
Type-File
Bitmaps
EH31523x.200
EH1523_d.bmp
EH1523_n.bmp
EH1523_s.bmp
TMT184
Manufacturer spec. GSD
Endress+Hauser