Model TCAEQY HE-A
Nominal cooling capacity (*)
EER
Nominal cooling capacity (*) (°) EN 14511:2013
EER (*) (°) EN 14511:2013
ESEER EN 14511:2013
Sound pressure (***) (*)
Sound power (****) (*)
Scroll/step compressor
Circuits
Fans
Heat exchanger
Water side heat exchanger nominal pressure drops (*)
Residual head P1 (*)
Residual head P2 (*)
Residual head ASP1 (*)
Residual head ASP2 (*)
Tank water content (ASP1/ASP2)
Nominal heating capacity RC100 (±)
Nominal heating capacity DS (±)
Amount of R410A refrigerant
Polyester oil charge
Electrical data
Pump absorbed power (P1/ASP1) / (P2/ASP2)
Electrical power supply
Auxiliary electrical
Pump absorbed current (P1/ASP1) / (P2/ASP2)
Dimensions
Height (a)
Width (b)
Length (c)
Heat exchanger inlet/outlet connections and RC100
DS inlet/outlet connections
Weight
(*) Under the following conditions: condenser inlet air temperature
35°C; chilled water temperature 7°C; temperature differential at
evaporator 5 K; fouling factor equal to 0.35x10-4 m2 K/W.
(***) Sound pressure level in dB(A) referring to a 10 m distance from
data refers to the units without the electric pump
(****) Sound power level in dB(A) on the basis of measurements taken
in accordance with UNI EN-ISO 9614 and Eurovent 8/1 Standards
The noise data refers to the units without the electric pump
Enclosed documents
2110 2120 2140 2150 2170 2200 2220 4240 4270 4310 4340
kW
101
109
127
2,77
2,63
2,73
4,98
4,84
4,81
kW
100,6 108,6 126,5 140,5 155,5 181,4 199,4 218,4 251,4 280,2 318,2
2,73
2,6
2,69
4,29
4,12
4,09
dB(A)
47
47
48
dB(A)
79
79
80
2/3
2/3
2/2
1
1
1
n° x kW
2x0,6 2x0,6 3x0,6 3x0,6 3x0,6 4x0,6 4x0,6 4x0,6 6x0,6 6x0,6 8x0,6
m³/h
23000 23000 33000 33000 34500 44000 44000 44600 60000 62600 75600
Type
Plates/Shell and tube (STE accessory)
m³/h
17,4
18,7
21,8
kPa
28
26
29
kPa
105
105
95
kPa
149
149
138
kPa
103
102
91
kPa
147
145
134
l
300
300
300
kW
141
156
176
m³/h/kPa
24,2/56 26,8/53 30,3/57 34,4/56 38,7/54 44/57 49,2/58 53,3/46 60,5/43 67,9/56 75,5/50
kW
26
29
34
m³/h/kPa 2,2/8 2,5/6 2,9/7 3,2/6 3,5/6
Kg
17
17
18
Kg
10,4
10,4
10,4
2110 2120 2140 2150 2170 2200 2220 4240 4270 4310 4340
kW
36,5
41,4
46,5
kW
1,5/2,2 1,5/2,2 1,5/2,2 2,2/3,0 2,2/3,0 2,2/3,0 2,2/3,0 3,0/4,0 3,0/4,0 4,0/5,5 4,0/5,5
V-ph-Hz
V-ph-Hz
A
61
69
77
A
81
91
102
A
243
261
264
A
159
177
180
A
3,0/4,5 3,0/4,5 3,0/4,5 4,5/6,0 4,5/6,0 4,5/6,0 4,5/6,0 6,0/8,0 6,0/8,0 8,0/10,5 8,0/10,5
2110 2120 2140 2150 2170 2200 2220 4240 4270 4310 4340
mm
2440 2440 2440 2440 2440 2440 2440 2030 2030 2030 2030
mm
1350 1350 1350 1350 1350 1350 1350 2090 2090 2090 2090
mm
3600 3600 3600 3600 4550 4550 4550 4800 4800 5300 5300
Ø
2"½ vic 2"½ vic 2"½ vic 2"½ vic 2"½ vic 2"½ vic 2"½ vic 3" vic 3" vic 3" vic 3" vic
Ø
1" GM 1" GM 1" GM 1" GM 1" GM 1" GM 1" GM 2" vic 2" vic 2" vic 2" vic
Kg
1250 1260 1270 1290 1440 1460 1480
(±) Recovery unit heating capacity Conditions referring to the unit
operating with chilled water temperature 7°C, differential temperature
due to evaporation of 5 K, hot water temperature produced equivalent
to 40/45°C (RC100) 50/60°C (DS). NB. With heat pumps operat-
ing in winter mode with DC active, the heating capacity available is
decreased from the portion supplied to the desuperheater.
( ) Absorbed current/absorbed power value without electric pump.
The starting current refers to the worst conditions of the unit.
(°) Data calculated in accordance with EN 14511:2011 under nominal
conditions.
The refrigerant charge values are indicative. Refer to the
serial number plate.
290
141
156
182
200
219
2,68
2,63
2,67
2,64
2,59
4,87
4,72
4,82
4,79
4,90
2,65
2,6
2,64
2,61
2,57
4,15
4,02
4,12
4,05
4,19
48
49
50
50
51
80
81
82
82
83
2/3
2/2
2/3
2/2
4/4
1
1
1
1
2
24,2
26,8
31,3
34,4
37,7
28
27
29
29
23
132
125
109
96
110
173
168
152
140
150
127
119
100
86
107
168
161
144
130
147
300
550
550
550
700
200
225
256
286
310
37
41
47
53
58
4/8
4,6/7
5/13 5,7/11 6,4/11 7,2/11
19
23
25
26
50
10,4
10,4
10,4
10,4
20,8
52,6
59,3
68,2
75,8
84,6
400 – 3 – 50
230 – 1 – 50
87
99
113
126
140
115
128
144
159
183
341
354
370
381
353
226
239
247
261
269
2420
252
281
319
2,71
2,65
2,65
4,96
4,97
4,85
2,68
2,62
2,63
4,22
4,21
4,14
53
53
54
85
85
86
4/4
4/4
4/4
2
2
2
43,3
48,3
54,8
23
28
26
97
121
104
139
178
159
93
115
97
135
172
153
700
700
700
352
395
439
66
74
84
53
58
63
20,8
20,8
20,8
93
106 120,4
154
176
200
195
229
251
365
455
485
281
353
370
2520 2650 2770