NORITZ AMERICA CORPORATION NCC199-SV Manuel D'installation page 14

Chauffe-eau à gaz sans cuve à condensation
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Horizontal Vent Termination- PVC/CPVC Materials Only
PVC/CPVC
Coupling
PVC/CPVC
Adapter*
Pipe Material
No. of Elbows
3
2
1
***Not including the termination.
Vertical Vent Termination- PVC/CPVC Materials Only
**0.3m (1')
Minimum
14
Hanger
Straps
Slope vent
Upwards
**0.3m (1')
Minimum
* Not supplied with water
heater, order separately.
**0.3m (1') minimum
recommended, but not required.
PVC or CPVC
Max. Straight Vent Length***
100mm (4") Pipe
75mm (3") Pipe
4.6m (15')
0.9m (3')
8.2m (27')
3m (10')
12.0m (39')
5.1m (17')
Storm
Collar
Roof
Flashing
Firestop/Support
Support
Firestop
Hanger
Strap
Slope vent
Upwards
PVC/CPVC
Coupling
PVC/CPVC
Adapter*
Not supplied with water
*
heater, order separately.
**0.3m (1') minimum
recommended, but not required.
Terminate at least 300mm (12") above
grade or above snow line.
Terminate at least 2.1m (7') above a public
walkway, 1.8m (6') from the combustion air
intake of any appliance, and 0.9m (3') from
any other building opening, gas utility
Insert Bird
meter, service regulator etc.
Screen* in
Each End
Terminate at least 0.9m (3') above any
of Tee
forced air inlet within 3m (10'), 1.2m (4')
below, 1.2m (4') horizontally from or 0.3m
(1') above any door, window, or gravity
air inlet into any building per National
Fuel Gas Code ANSI Z223.1/NFPA 54.
A tee or 45° elbow may be used for the
termination.
Slope the horizontal vent 1/4" upwards for
every 300mm (12") toward the termination.
Use a condensation drain if necessary.
In the Commonwealth of Massachusetts
a carbon monoxide detector is required
for all side wall horizontally vented gas
fuel equipment. Please refer to Technical
Bulletin TB 010606 for full installation
instructions.
Insert Bird
Screen* in
Terminate at least from the combustion air
End of 45°
intake of any appliance, and 0.9m (3') from
Elbow
any other building opening, gas utility meter,
service regulator etc.
Enclose exterior vent systems below the
roof line to limit condensation and protect
against mechanical failure.
When the vent penetrates a floor or ceiling
and is not running in a fire rated shaft, a
firestop and support is required.
When the vent termination is located not
less than 2.4m (8') from a vertical wall or
similar obstruction, terminate above the
roof at least 0.6m (2'), but not more than
1.8m (6'), in accordance with the National
Fuel Gas Code ANSI Z223.1/NFPA 54.
Provide vertical support every 0.9m (3') or
as required by the vent pipe manufacturer's
instructions.
A short horizontal section is recommended
to prevent debris from falling into the water
heater.
When using a horizontal section, slope the
horizontal vent 1/4" upwards for every
300mm (12") toward the termination to
drain condensate.