Ul-Data - DOLD SAFEMASTER S LH 5946 Traduction De La Notice Originale

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Technical Data
General Data
Nominal operating mode:
Temperature range
Operation:
Storage:
Altitude:
Clearance and creepage distance
Rated impulse voltage / pollution degree:
Contacts 11/12, 23/24,
33/34, 43/44 against all others:
Contacts 11/12, 23/24,
33/34, 43/44 against each others: 4 kV / 2
Indicator contact 53/54
against all others:
Semiconductor outputs A3+/
ON / ERR / A4 against all others: 6 kV / 2
Auxiliary voltage A1 / A2
against all others:
At auxiliary voltage AC:
At auxiliary voltage DC:
Control terminal X1 / X2 / X3:
EMC
Interference suppression
Auxiliary voltage AC:
Auxiliary voltage DC:
Degree of protection
Housing:
Terminals:
Enclosure:
Vibration resistance:
Climate resistance:
Terminal designation:
Wire connection:
Wire fixing:
Mounting:
Weight:
Dimensions
Width x height x depth:
Continuous operation
- 25 ... + 60 °C
(+ 40°C with max. contact current,
see Derating)
- 40 ... + 75 °C
≤ 2000 m
IEC 60664-1
6 kV / 2
4 kV / 2
6 kV / 2
4 kV / 2
No galvanic separation to L1 / L2 / L3
IEC/EN 61326-3-1, EN61000-6-7
Limit value class B
EN 55011
Limit value class A*
)
EN 55011
*
)
The device is designed for the usage
under industrial conditions (Class A,
EN 55011). When connected to a low
voltage public system (Class B, EN 55011)
radio interference can be generated.
To avoid this, appropriate measures have
to be taken.
IP 40
IEC/EN 60529
IP 20
IEC/EN 60529
Thermoplastic with VO behaviour
according to UL subject 94
Amplitude 0.35 mm
Frequency 10 ... 55 Hz, IEC/EN 60068-2-6
25 / 060 / 04
IEC/EN 60068-1
EN 50005
DIN 46228-1/-2/-3/-4
Plus-minus terminal screws M 3.5
box terminals with wire protection or
cage clamp terminals
DIN-rail
IEC/EN 60715
Approx. 400 g
45 x 90 x 121 mm

UL-Data

The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, "general use
applications"
Auxiliary voltage U
H
for DC 24 V:
Measuring-/Motor voltage:
Ambient temperature:
Switching capacity
safety contacts
(11/12, 23/24, 33/34, 43/44)
Ambient temperature 40 °C:
Ambient temperature 60 °C:
Switching capacity
indicator contact (53/54)
Wire connection:
Fixed screw terminal:
Plug in screw terminal:
Plug in cage clamp terminal:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo
24
Device must be supplied with a Class 2 or
a voltage / current limited power supply
(max. 4 A).
Max. AC 600 V
- 25 ... + 60 °C, (+ 40 °C with max. contact
current, see Derating)
Pilot duty B300
5A 250Vac G.P.
5A 24Vdc G.P.
Pilot duty B300
2A 250Vac G.P.
2A 24Vdc G.P.
3A 250Vac G.P.
60 °C / 75 °C copper conductors only
1 x AWG 20 - 12 Sol/Str Torque 0.8 Nm or
2 x AWG 20 - 14 Sol/Str Torque 0.8 Nm
AWG 20 - 14 Sol Torque 0.8 Nm or
AWG 20 - 18 Str Torque 0.8 Nm
AWG 20 - 12 Sol/Str
LH 5946 / 22.03.22 en / 530A

Publicité

Table des Matières
loading

Table des Matières