Technical Data; Ul-Data; Standard Type - DOLD SAFEMASTER LG 7928 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Technical Data

Input
Nominal voltage U
:
N
Voltage range:
Nominal frequency:
Nominal consumption:
Control voltage on S11:
Control current in Y1, Y2:
Short-circuit protection:
Überspannungsschutz:
Output
Contacts
LG 7928.97:
LG 7928.98:
ATTENTION! The NC contacts 45-46 can only be used for monitoring.
Contact type:
Release delay typ. at U
:
N
Disconnecting the supply:
Disconnecting Y1, Y2:
Time delay t
:
v
Repeat accuracy:
Thermal current I
:
th
Switching capacity
to AC 15
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
Electrcal life:
at 5 A, AC 230 V cos. j = 1:
Permissible switching
frequency:
Short circuit strength
Max. fuse rating:
Mechanical life:
DC 24 V
AC/DC 24 V
0.9 ... 1.1 U
N
50 / 60 Hz
Typ. DC 2.0 W
typ. AC 3.5 VA
Min. DC 20 V at U
N
Typ. DC 2,2 mA at U
N
typ. AC 3,1 mA at U
N
Internal with PTC
Internal with VDR
3 NO contacts, 2 NC contacts
4 NO contacts, 1 NC contacts
Forcibly guided
35 ms
40 ms
adjustable
fixed
0.1 ...
1 s
1 s
0.3 ...
3 s
3 s
0.5 ...
5 s
5 s
1.0 ... 10 s
10 s
3.0 ... 30 s
30 s
6.0 ... 60 s
60 s
30.0 ... 300 s
300 s
60.0 ... 600 s
600 s
Other time ranges on request
± 1% of setting value
Max. 5 A (see quadratic total current limit curve)
3 A / AC 230 V
IEC/EN 60947-5-1
2 A / AC 230 V
IEC/EN 60947-5-1
2 A / DC 24 V
IEC/EN 60947-5-1
2 A / DC 24 V
IEC/EN 60947-5-1
4 A / 24 V at 0.1 Hz
4 A / 24 V at 0.1 Hz
> 2.2 x 10
5
switch. cycl. IEC/EN 60947-5-1
Max. 2000 switching cycles / h
with manual restart and short
release delay time
6 A gG / gL
IEC/EN 60947-5-1
20 x 10
switching cycles
6
Technical Data
General Data
Nominal operating mode:
Temperaturr range
Operation:
Strorage:
Altitude:
Clearance and creepage distance
Rated impulse voltage /
pollution degree:
EMC
Interference suppression:
Degree of protection
Housing:
Terminals:
Housing:
Vibration resistance:
Climate resistance:
Terminal designation:
Wire fixing:
Mounting:
Weight:

UL-Data

The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, "general use
applications"
Nominal voltage U
:
N
Ambient temperature:
Switching capacity:
Ambient temperature 45°C:
Ambient temperature 55°C:
Wire connection:
Screw terminals fixed:
Plug in screw:
Plug in cage clamp:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo

Standard Type

LG 7928.97/61 AC/DC 24 V 1 ... 10 s
Article number:
• Output:
• Nominal voltage U
:
N
• Time delay t
:
v
• Width:
14
Continuous operation
- 15 ... + 55°C
- 25 ... + 85°C
≤ 2000 m
4 kV / 2
IEC 60664-1
IEC/EN 61326-3-1, IEC/EN 62061
Limit value class B
IP 40
IEC/EN 60529
IP 20
IEC/EN 60529
Thermoplastic with VO behaviour
according to UL subject 94
Amplitude 0.35 mm
Frequency 10 ... 55 Hz, IEC/EN 60068-2-6
15 / 055 / 04
IEC/EN 60068-1
EN 50005
Plus-minus terminal screws M 3.5
box terminals with wire protection or
cage clamp terminals
DIN rail
IEC/EN 60715
Approx. 190 g
AC/DC 24 V
-15 ... +55°C
Pilot duty B300
5A 250Vac Resistive
5A 24Vdc Resistive or G.P.
Pilot duty B300
4A 250Vac Resistive
4A 24Vdc Resistive or G.P.
60°C / 75°C copper conductors only
AWG 20 - 12 Sol/Str Torque 0.8 Nm
AWG 20 - 14 Sol Torque 0.8 Nm
AWG 20 - 16 Str Torque 0.8 Nm
AWG 20 - 12 Sol/Str
0062796
3 NO contacts, 2 NC contacts
AC/DC 24 V
1 ... 10 s
22.5 mm
LG 7928 / 29.04.21 en / 390A
EN 55011

Publicité

Table des Matières
loading

Table des Matières