Ul-Data; Standard Type; Variants; Troubleshooting - DOLD SAFEMASTER C UG 6961 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

UL-Data

The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, "general use
applications"
Ambient temperature:
Altitude:
Switching capacity for .02:
Switching capacity for .04
Ambient temperature 55°C
Ambient temperature 40°C:
Wire connection::
PS-terminal:
PC-terminal:
PT-terminal:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo

Standard Type

UG 6961.02PS/100/61 DC24V 300 s
Article number:
• Safety function:
• Delay function:
• Time delay:
• Output:
• Nominal voltage:
• Width:
- 15 ... + 55 °C
≤ 2000 m
Pilot duty B300, Q300
8A 250Vac Resistive or G.P.
8A 24Vdc Resistive
Pilot duty B300, Q300
5A 250Vac Resistive or G.P.
5A 24Vdc Resistive
Pilot duty B300, Q300
8A 250Vac Resistive or G.P.
8A 24Vdc G.P.
60°C / 75°C copper conductors only
AWG 28 - 12 Sol/Str Torque 0.5 Nm
AWG 24 - 12 Sol/Str
AWG 24 - 16 Sol/str
0065425
E-stop
Adjustable
Adjustable
2 NO contacts
DC 24 V
22.5 mm

Variants

UG 6961 ._ _ _ _ / _ _ _ /61 DC 24 V 300 s

Troubleshooting

Failure
LED "ON" does not light up
LED "ERR" flashes
in relation 1:1
LED "ERR" flashes
in relation 4:1
LED "ERR"
continuously on

Maintenance and Repairs

- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
22
max. time range or fixed time
Nominal voltage
UL-approval
Time delay
0 = Adjustable
1 = Fixed
Delay function
0 = Adjustable
Safety function
1 = E-stop,
with cross fault detection
2 = Safety gate,
with cross fault detection
3 = Two-hand control,
with cross fault detection
4 = Safety mat / Safety edge,
with cross fault detection
5 = Exclusive or contacts,
with cross fault detection
6 = E-stop,
without cross fault detection
7 = Safety gate,
without cross fault detection
8 = Light curtain,
without cross fault detection
Type of terminals
PC (plug in cage clamp):
pluggable terminal blocks,
with cage clamp terminals
PS (plug in screw):
pluggable terminal blocks,
with screw terminals
PT (plug in Twin cage clamp):
pluggable terminal blocks,
with cage clamp terminals 2-wire
Contacts
Type
Potential cause
- Power supply A1+/A2
not connected
- Under- or overvoltage
(check power supply A1+/A2)
- external failure (see flashing code)
- system error
(if cannot be removed after restart
unit must be replaced)
UG 6961 / 08.07.19 en / 214A