Start-Up Procedure - ABB BEHA OTOMASYON ACS 850 Guide Rapide

Masquer les pouces Voir aussi pour BEHA OTOMASYON ACS 850:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 62
4 Quick Start-up Guide for ACS850 with Standard Control Program

Start-up procedure

The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the
safety instructions on the first pages of the appropriate hardware manual.
Check the installation. See the installation checklist in the appropriate hardware
manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if
• there is a risk of damage in case of an incorrect direction of rotation, or
• a normal ID run is required during the drive start-up, when the load torque is higher
than 20% or the machinery is not able to withstand the nominal torque transient
during the ID run.
Connect the control panel to the drive using an
appropriate Category 5E cable.
Power up the drive. After a few moments, the panel
shows the Output mode (right).
Note: The Output mode display will alternate with
"Alarm 2021 NO MOTOR DATA" until motor data is
entered later in this procedure.
Switch to local control to ensure that external control
is disabled by pressing the
panel. Local control is indicated by the text "LOC" on
the top row on the display.
The two boxes on the bottom row of the display
indicate the function of the two soft keys
. The contents of the boxes depend on the
visible menu choices.
Press
(MENU) to access the Main menu.
Within any menu, the desired selection is
highlighted. Press the
make a new choice; activate by pressing
(ENTER).
The Main menu is the starting point for the
procedures described below.
Notes:
• At any point, press
• By default, not all parameters are visible. Set parameter 16.15 Menu set sel to Load
long to make all parameters visible.
www.behaotomasyon.com
Safety
Power-up, control panel basics
LOC
key on the control
REM
and
Adjusting parameter values
(CANCEL or EXIT) to return to the previous level.
www.behaotomasyon.com
REM
DIR
LOC
DIR
and
LOC
MAIN MENU
PARAMETERS
ASSISTANTS
keys to
CHANGED PAR
EXIT
0.00rpm
0.
00
Hz
0.
00
A
0.
0
%
MENU
0.00rpm
0.
00
Hz
0.
00
A
0.
0
%
MENU
1
ENTER

Publicité

Table des Matières
loading

Table des Matières