ABB BEHA OTOMASYON ACS 850 Guide Rapide page 9

Masquer les pouces Voir aussi pour BEHA OTOMASYON ACS 850:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 62
8 Quick Start-up Guide for ACS850 with Standard Control Program
Select the motor control mode. DTC is suitable for
most cases.
Scalar mode is recommended if
• the nominal current of the motor is less than 1/6
of the nominal current of the drive,
• the drive is used for test purposes with no motor
connected, or
• the drive controls multiple motors and the number
of motors connected is variable.
Enter the motor data from the motor nameplate.
Asynchronous motor nameplate example:
3
motor
Hz
V
690 Y
50
400 D
50
660 Y
50
380 D
50
50
415 D
440 D
60
Cat. no
3GAA 202 001 - ADA
6312/C3
Permanent magnet motor nameplate example:
ABB Motors
3 ~ motor
M2BJ 280SMB 10 B3
S1 SPEC INSUL.
JK-21640-1
V
Hz
kW
400 D
50
55
Prod. code
2GBJ285220-ADA405445477
6316/C3
• motor nominal current
Allowed range: approximately 1/6 × I
the drive (0...2 × I
mode = Scalar).
www.behaotomasyon.com
ABB Motors
M2AA 200 MLA 4
IEC 200 M/L 55
No
Ins.cl. F
kW
r/min
A
cos
30
1475
32.5
0.83
56
30
1475
0.83
1470
34
0.83
30
30
1470
59
0.83
1475
54
0.83
30
35
1770
59
0.83
6210/C3
IEC 34-1
No 3424522
Ins.cl. F
IP 55
cos M
r/min
A
IA/IN
600
103
0.97
6316/C3
630kg
IEC 34-1
Hd
if parameter 99.05 Motor ctrl
Hd
www.behaotomasyon.com
99.05 Motor ctrl mode
Note: Set the motor data to
exactly the same value as on the
motor nameplate. For example, if
the motor nominal speed is 1470
rpm on the nameplate, setting the
value of parameter 99.09 Mot
nom speed to 1500 rpm results in
incorrect operation of the drive.
IP 55
IA/IN t E/s
If D (delta) data is chosen, then
connect the motor in delta.
If Y (star) data is selected, then
connect the motor in star.
180
t
E/s
99.06 Mot nom current
... 2 × I
of
Hd

Publicité

Table des Matières
loading

Table des Matières