Output control

This control strategy is used when the heating system is controlled using
a building management system with a 0-10 V controller output.
P / %
100
10
1
1,5
Fig. 1
Linear relationship between the 0-10 V signal (U in volts) and
required performance P (in percent with reference to the
maximum system performance)
The connected heat sources are turned on and off according to the
required performance as per the module code as is the case with a serial
standard or serial optimized cascade.
2.2.6

Flow temperature control

This control strategy is used when the heating system is controlled using
a building management system with a 0-10 V controller output.
/ %
max
min
1
1,5
Fig. 2
Linear relationship between the 0-10 V signal (U in volts) and
required flow temperature
maximum flow temperature)
The connected heat sources are turned on and off according to the
required flow temperature as per the module code as is the case with a
serial standard or serial optimized cascade.
MC 400
U / V
10
6 720 809 449-21.1O
U / V
10
6 720 809 449-22.1O
(in percent with reference to the
2.3

Setting the coding card

2
1
Fig. 3
Coding card with module status display, and a status display of
the connected heat sources or modules
Coding
Module function
0
Off (delivered condition)
1
Serial standard cascade
2
Serial optimized cascade ( Fig. 23, page 85)
3
Serial cascade with peak load coverage
4
Parallel cascade
5
No function
6
External 0-10 V performance control with serial standard cascade
7
External 0-10 V performance control with serial optimized cascade
( Fig. 24, page 86)
8
External 0-10 V flow temperature control with serial standard
cascade
9
External 0-10 V flow temperature control with serial optimized
cascade
10
The module is one of a maximum of 4 subordinate cascade modules.
The higher level cascade modules control the connected heat source
corresponding to the code noted on them ( Fig. 25, page 86).
Table 2 Coding and function
2.4

Scope of delivery

Fig. 4, page 82:
[1]
Module
[2]
Bag with strain relief
[3]
Installation instructions
2.5

Specifications

The design and operation of this product comply with
European Directives and the supplementary national
requirements. Its conformity is demonstrated by the CE
marking . You can ask for a copy of the declaration of conformity for this
product. For this purpose see the contact address on the back cover of
these instructions.
Specifications
Dimensions (W × H × D)
Maximum conductor cross-section
• 230 V terminal
• Extra-low voltage terminal
Rated voltages
• BUS
• Module mains voltage
• User interface
• Pumps and mixers
Fuse
BUS interface
Power consumption on – standby
Max. output
Table 3
Product details | 13
4
3
S
Y
0
I
6 720 810 538-23.1O
246 × 184 × 61 mm (further
dimensions  Fig. 5, page 82)
2
• 2.5 mm
2
• 1.5 mm
• 15 V DC
(reverse-polarity-protected)
• 230 V AC, 50 Hz
• 15 V DC
(reverse-polarity-protected)
• 230 V AC, 50 Hz
230 V, 5 AT
EMS 2 /EMS plus
< 1 W
1100 W
6 720 816 739 (2015/05)