Vortice REG FILTER Notice D'emploi Et D'entretien page 38

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Record 51: Current fan speed [read-only].
High Byte: The value that is sent is the speed value (0% to 100%) in 16-bit binary.
Low Byte: The value that is sent is the voltage value (0.0 to 10.0V) multiplied by 10 in 16-bit binary.
This voltage value corresponds to the analog output of the regulator for the fan speed (terminals 19 and 20).
Fan operation (voltage):
OFF
0.0
V
ON
0% 0.0V
1% Minimum voltage (Record7)
...
100% Maximum voltage (Record 8) End of line resistance configuration
Fan operation
Record 52: Filter status (by timer) [read-
only].
High byte: G4 filter.
0: Filter clean.
1: Dirty filter.
Low byte: H14 filter.
0: Filter clean.
1: Dirty filter.
Record 53: Current status UV-C lamp
[read only].
0: Off (UV-C lamp deactivated - relay
contact open). 1: On (UV-C lamp activated
- relay contact closed).
UV-C lamp operation
Record 54: Firmware version [read-only].
The value that is sent is the value of the controller software version (XX.X) multiplied by 10 in 16-bit binary.
Note: When powering the regulator, or after a reset, it displays the firmware version on the display (v X.X).
38

Publicité

Table des Matières
loading

Table des Matières