S+S Regeltechnik AERASGARD RFTM-LQ-PS-CO2-MODBUS Notice D'instruction

Sonde d'ambiance multifonctions
Masquer les pouces Voir aussi pour AERASGARD RFTM-LQ-PS-CO2-MODBUS:

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

D G F r
6000-3790-0000-2XX 37900-2021 V200 02 ⁄ 2021
RFTM - LQ - PS - CO2 - Modbus
AERASGARD
® 
D
Bedienungs- und Montageanleitung
Multifunktionaler Raumfühler bzw. Messumformer
für Feuchte, Temperatur, Luftqualität (VOC), Feinstaub (PM) und CO2 - Gehalt,
kalibrierfähig, mit Modbus-Anschluss
G
Operating Instructions, Mounting & Installation
Multifunctional room sensor and measuring transducer
for humidity, temperature, air quality (VOC), fine dust (PM) and CO2 content,
calibratable, with Modbus connection
F
Notice d'instruction
Sonde d'ambiance multifonctions, resp. convertisseur de mesure,
pour l'humidité, la température, la qualité de l'air (COV), les particules fines (PM)
et la teneur en CO2, étalonnable, avec raccordement Modbus
r
Руководство по монтажу и обслуживанию
Мультифункциональный датчик для помещений ⁄ измерительный преобразователь
для измерения влажности, температуры, качество воздуха (VOC),
мелкая пыль (ТЧ) и содержания CO2, калибруемый, с подключением к шине Modbus
S+S REGELTECHNIK GMBH
THURN-UND-TAXIS - STR. 22
90411 NÜRNBERG ⁄ GERMANY
FON +49 ( 0 ) 911 ⁄ 5 19 47- 0
mail@SplusS.de
www.SplusS.de
CARTONS
ET EMBALLAGE
PAPIER À TRIER

Publicité

Table des Matières
loading

Sommaire des Matières pour S+S Regeltechnik AERASGARD RFTM-LQ-PS-CO2-MODBUS

  • Page 1 Руководство по монтажу и обслуживанию Мультифункциональный датчик для помещений ⁄ измерительный преобразователь для измерения влажности, температуры, качество воздуха (VOC), мелкая пыль (ТЧ) и содержания CO2, калибруемый, с подключением к шине Modbus S+S REGELTECHNIK GMBH THURN-UND-TAXIS - STR. 22 90411 NÜRNBERG ⁄ GERMANY CARTONS FON +49 ( 0 ) 911 ⁄...
  • Page 2 D G F r RFTM - LQ - PS - CO2 - Modbus AERASGARD ®  Maßzeichnung R CO2 - Modbus Dimensional drawing RLQ - CO2 - Modbus Plan coté RFTM - CO2 - Modbus Габаритный чертеж RFTM - LQ - CO2 - Modbus 32.6 Maßzeichnung RFTM - CO2 - Modbus - P...
  • Page 3: Technische Daten

    AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 Multifunktionaler Raumklimafühler AERASGARD ® RFTM - LQ - PS - CO2 - Modbus (maximale Ausbaustufe) mit Modbus- Anschluss, im formschönen Kunststoffgehäuse mit Schnappdeckel, Unterteil mit 4-Loch -Befestigung, wahlweise mit ⁄ ohne Display, Typenvariante RFTM - CO2 - Modbus wahl- weise mit ⁄...
  • Page 4 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 R xx - Modbus RFTM - CO2 - Modbus - P Schaltbild Schaltbild (mit Potentiometer) DIP A: Busadresse Sensor Stecker Stecker DIP B: Busparameter Display Display (Baudrate, Parity ...) Telegramm-Anzeige.
  • Page 5 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 ACHTUNG !  Die minimale CO2 - Konzentration von Außenluft beträgt in begrünten, industrie armen Gegenden ca. 350 ppm. Der Gas austausch im Sensorelement erfolgt durch Diffusion. Je nach Konzentrationsänderung und Strömungs geschwindigkeit der Luft in Sensor umgebung kann die Reaktion des Gerätes auf die Konzentrationsänderung verzögert auftreten.
  • Page 6 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Konfiguration Rev. 2020 - V31 intro BUSADRESSE MODBUS Busadresse (binärcodiert, Wertigkeit 1 bis 247 einstellbar) DIP-Schalter [ A ] DIP 1 DIP 2 DIP 3 DIP 4 DIP 5 DIP 6 DIP 7 DIP 8...
  • Page 7: Anzeige Im Display

    AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Konfiguration ANZEIGE IM DISPLAY Standardmäßig werden im Display die Mess werte mit den entsprechenden Einheiten zyklisch nacheinander angezeigt: CO2-Gehalt in ppm, Luft qualität (VOC) in %, Temperatur in °C, relative Feuchte in % r.H., Feinstaub (PM) in µg/m Über die Modbusschnittstelle kann anstelle der Standard-Anzeige eine alternative Ausgangs größe programmiert werden: CO2-Gehalt in ppm, Luft qualität (VOC) in %, Temperatur in °C, relative Feuchte in % r.H., Feinstaub (PM) in µg/m Hierbei wird in der ersten Zeile der Wert mit Index und in der zweiten Zeile die entsprechende Einheit statisch angezeigt.
  • Page 8 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Konfiguration, Telegramme ASCII-Code-Tabelle für Dot Matrix Anzeigebereich ASCII Sign ASCII Sign ASCII Sign ASCII Sign ASCII Sign Leer “ & < > ü ä Ä ö Ö Ü °...
  • Page 9 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Telegramme TELEGRAMME Function 06 Write Single Register & Function 16 Write Multiple Register Register Parameter (Display) Data Type Value Range 4x0001 physikalischer Anzeigewert Index im Display Unsigned 8 Bit 0...10 0...10 Standardanzeige (zyklisch):...
  • Page 10 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Telegramme TELEGRAMME Function 08 Diagnostics Folgende Sub Function Codes werden unterstützt Sub Function Parameter Data Type Antwort Code Echo der Sendedaten Echodaten (Loopback) Neustart Modbus Echo Telegramm (Reset Listen Only Mode) Aktivierung Listen Only Mode Keine Antwort Lösche Zähler...
  • Page 11 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Installation Rev. 2015 - 1.0 intro Allgemeiner Aufbau Busstruktur MODBUS RTU-Master Passiver Aktiver Abzweig Abzweig RS-485 Leitungs- Leitungs- Stammleitung abschluss abschluss (Trunk-Kabel) Stichleitung (Drop-Kabel) Slave n Stichleitung: Mehrfachabzweigung n: Slave 1 Slave 2 kürzer 20m...
  • Page 12 Montage und Inbetriebnahme Die Geräte sind im spannungslosen Zustand anzuschließen. Der Hinweise zur Montage: Der Einbau hat unter Berücksichtigung der einschlägigen, für den Anschluss der Geräte darf nur an Sicherheitskleinspannung Mess ort gültigen Vorschriften und Standards (wie z. B. Schweiß vor- er folgen.
  • Page 13: Wichtige Hinweise

    Wichtige Hinweise Als AGB gelten ausschließlich unsere sowie die gültigen „Allgemeinen Lieferbedingungen für Erzeugnisse und Leistungen der Elektro industrie“ (ZVEI Bedingungen) zuzüglich der Ergänzungsklausel „Erweiterter Eigentumsvorbehalt“. Außerdem sind folgende Punkte zu beachten: – Der Anschluss der Geräte darf nur an Sicherheitskleinspannung und im spannungslosen Zustand erfolgen. Um Schäden und Fehler am Gerät (z.B.
  • Page 14: Technical Data

    AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 Multifunctional indoor climate sensor AERASGARD ® RFTM - LQ - PS - CO2 Modbus (maximum expansion level) with Modbus connection, in an elegant plastic housing with snap-on lid, base with 4-hole attachment, optionally with ⁄ without display, type variant RFTM - CO2 Modbus optionally with ⁄ without setpoint potentiometer.
  • Page 15 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 R xx - Modbus RFTM - CO2 - Modbus - P Schematic diagram Schematic diagram DIP A: Bus address Sensor Plug for Plug for DIP B: Bus parameters display display (Baud rate, parity ...)
  • Page 16 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 ATTENTION !  The minimum CO2 concentration of outdoor air amounts to approx. 350 ppm in leafy, hardly industrialised areas. Gas inter-exchange in the sensor element happens by diffusion. Depending on the changes to the concentration and the flow velocity of the air surrounding the sensor, the reaction of the device to the change of concentration may take place with a delay.
  • Page 17 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Configuration Rev. 2020 - V31 intro BUS ADDRESS MODBUS Bus address (binary coded, value selectable from 1 to 247) DIP switch [ A ] DIP 1 DIP 2 DIP 3 DIP 4 DIP 5...
  • Page 18 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Configuration READOUT IN THE DISPLAY By default, the display indicates the following measurements with the corresponding units cyclically and consecutively: CO2 content in ppm, air quality (VOC) in %, temperature in °C, relative humidity in % r.H., particulate matter (PM) in µg/m The Modbus interface can be used to program an alternative output variable instead of the standard display: CO2 content in ppm, air quality (VOC) in %, temperature in °C, relative humidity in % r.H., particulate matter (PM) in µg/m In this case, the first line indicates the value and indexwhile the second line indicates the corresponding unit statically.
  • Page 19 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Configuration, Telegrams ASCII Code Table for Dot Matrix Display Area ASCII Sign ASCII Sign ASCII Sign ASCII Sign ASCII Sign Blank “ & < > ü ä Ä ö...
  • Page 20 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Telegrams TELEGRAMS Function 06 Write Single Register & Function 16 Write Multiple Register Register Parameter (display) Data Type Value Range 4x0001 Physical parameter displayed Index on display Unsigned 8 bit 0…10 0…10 Standard display (cyclic):...
  • Page 21 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Telegrams TELEGRAMS Function 08 Diagnostics The following sub function codes are supported Sub Function Parameter Data Type Answer Code Echo of transmission data Echo data (Loopback) Restart Modbus Echo telegram (Reset listen-only mode) Activation listen-only mode...
  • Page 22 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Installation Rev. 2017 - V14 intro General layout of bus structure MODBUS RTU-Master Passive Active branch branch RS-485 Line Line Trunk line termination termination Stub line Slave n Stub line: Multiple branch n: Slave 1...
  • Page 23 Installation and Commissioning Devices are to be connected under dead-voltage condition. Devices Notes on installation: Mounting shall take place while observing all relevant regulations and must only be connected to safety extra-low voltage. Consequential standards applicable for the place of measurement (e.g. such as weld- damages caused by a fault in this device are excluded from warranty ing instructions, etc.).
  • Page 24 Important notes Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.
  • Page 25 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 Sonde radio d’ambiance multifonctions AERASGARD ® RFTM - LQ - PS - CO2 - Modbus (équipement maximal) avec raccordement Modbus, boîtier plastique élégant avec couvercle emboîté, partie inférieure avec fixation à 4  trous, au choix avec/sans écran, version du modèle RFTM - CO2 - Modbus au choix avec/sans potentiomètre de consigne.
  • Page 26 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 R xx - Modbus RFTM - CO2 - Modbus - P Schéma de raccordement Schéma de raccordement DIP A: Bus address Sensor Plug for Plug for DIP B: Bus parameters display display...
  • Page 27 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 ATTENTION !  La teneur minimale en CO2 de l'air extérieur dans des régions vertes à faible degré d'industrialisation est de l'ordre 350 ppm. L'échange de gazdans l'élément capteur s'effectue par diffusion.
  • Page 28: Paramètres Du Bus

    AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Configuration Rev. 2020 - V31 intro ADRESSE DU BUS MODBUS Adresse du bus (code binaire, valance réglable de 1 à 247) Interrupteur DIP [ A ] DIP 1 DIP 2 DIP 3 DIP 4...
  • Page 29: Affichage Sur L'écran

    AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Configuration AFFICHAGE SUR L'ÉCRAN Par défaut, les valeurs de mesure suivantes sont affichées de manière cyclique, les unes après les autres dans l'écran avec les unités correspondantes : Teneur en CO2, qualité de l'air (COV) en %, température en °C, humidité relative en % h.r., particules fines (PM) en µg/m³ Via l'interface Modbus, l'affichage d'une dimension de sortie alternative peut être programmée au lieu de l'affichage standard : Teneur en CO2 en ppm, qualité...
  • Page 30 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Configuration Tableau des codes ASCII pour la zone d'affichage de la matrice de points ASCII Sign ASCII Sign ASCII Sign ASCII Sign ASCII Sign Espace “ & < >...
  • Page 31 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Télégrammes TÉLÉGRAMMES Function 06 Write Single Register & Function 16 Write Multiple Register Registre Paramètres (écran) Data Type Value Range 4x0001 Valeur d'affichage physique Indice à l'écran Unsigned 8 Bit 0...10 0...10 Affichage standard (cyclique) :...
  • Page 32 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Télégrammes TÉLÉGRAMMES Function 08 Diagnostics Les codes sous-fonction suivants sont pris en charge Code sous- Paramètre Data Type Réponse fonction Écho des données d'émission Données d'écho (loopback-rebouclage) Redémarrage Modbus Télégramme d'écho (Reset Listen Only Mode –...
  • Page 33 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Installation Rev. 2017 - V14 intro Structure générale du bus MODBUS RTU-Master Raccord Raccord actif passif RS-485 Fin de ligne Fin de ligne Ligne principale (câble principal) Tronçon (câble de dérivation) Slave n...
  • Page 34: Montage Et Mise En Service

    Montage et mise en service Les raccordements électriques doivent être exécutés HORS TENSION. Consignes demontage : L'installation doit être effectuée en conformité avec les réglementa- Veillez à ne brancher l’appareil que sur un réseau de très basse tension tions et les normes en vigueur pour le lieu de mesure (par ex. de sécurité.
  • Page 35: Généralités

    Généralités Seules les CGV de la société S+S, les « Conditions générales de livraison du ZVEI pour produits et prestations de l'industrie électronique » ainsi que la clause complémentaire « Réserve de propriété étendue » s'appliquent à toutes les relations commerciales entre la société S+S et ses clients.
  • Page 36: Технические Данные

    AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 Многофункциональный датчик для помещений AERASGARD ® RFTM - LQ - PS - CO2 - Modbus (максимальная модификация) с возможностью подключения к шине Modbus, в элегантном пластиковом корпусе с защелкивающейся крышкой и четырьмя отверстиями для крепления в нижней части, на...
  • Page 37 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 R xx - Modbus RFTM - CO2 - Modbus - P Схема подключения Схема подключения DIP A: Bus address Sensor Plug for Plug for DIP B: Bus parameters display display (Baud rate, parity ...)
  • Page 38 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus Rev. 2021 - V30 ВНИМАНИЕ!  Минимальная концентрация CO2 в наружном воздухе в озелененных районах с малым количеством промышленных объектов составляет прибл. 350 млн . Газообмен в чувствительном элементе осуществляется благодаря диффузии. В зависимости от изменения концентрации и скорости потока...
  • Page 39 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Конфигурация Rev. 2020 - V31 intro А ДРЕС ШИНЫ MODBUS Адрес шины (двоичный, настраиваемая значимость от 1 до 247) DIP-переключатель [ A ] DIP 1 DIP 2 DIP 3 DIP 4 DIP 5 DIP 6...
  • Page 40: Индикация На Дисплее

    AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Конфигурация ИНДИКАЦИЯ НА ДИСПЛЕЕ В стандартном исполнении на дисплее поочередно и циклично отображаются следующие измеренные значения с соответствующими единицами измерения: содержание углекислого газа (млн ), качество воздуха (VOC; %), температура (°C), относительная влажность...
  • Page 41 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Конфигурация Таблица кодов ASCII для полей с точечной матрицей ASCII Символ ASCII Символ ASCII Символ ASCII Символ ASCII Символ Пробел “ & < > ü ä Ä ö Ö...
  • Page 42 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Телеграммы ТЕЛЕГРАММЫ Функция 06 — Запись значения в один регистр хранения (Write Single Register) и функция 16 — Запись значений в несколько регистров хранения (Write Multiple Register) Регистр Параметры (дисплей) Тип...
  • Page 43 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Телеграммы ТЕЛЕГРАММЫ Функция 08 — Диагностика (Diagnostics) Поддерживаются следующие коды подфункции Код Параметр Тип данных Ответ подфункции Эхо отправленных данных Данные эхо (Loopback) Перезапуск Modbus Телеграмма эхо (Reset Listen Only Mode) Активация...
  • Page 44 AERASGARD ® RFTM - LQ - PS - CO2 - Modbus | Подключение Rev. 2017 - V14 intro Общая структура шины MODBUS RTU-Master Пассивное Активное ответвление ответвление RS-485 Оконечная Оконечная Магистральная нагрузка нагрузка линия шины шины (магистральный кабель) Тупиковая линия (ответвитель- Slave n ный...
  • Page 45: Монтаж И Ввод В Эксплуатацию

    Монтаж и ввод в эксплуатацию Приборы следует устанавливать в обесточенном состоянии. Указания по монтажу: Монтаж должен осуществляться с учетом соответствующих, Подключение должно осуществляться исключительно к безопасно действительных для места измерения предписаний и стандартов малому напряжению. Повреждения приборов вследствие (например, инструкции для сварочных работ). В особенности следует...
  • Page 46: Важные Указания

    Важные указания В качестве общих коммерческих условий действуют исключительно наши условия, а также действительные «Общие условия поставки продукции и услуг для электрической промышленности» (ZVEI), включая дополнительное условие «Оговорка о сохранении права собственности». Помимо этого, следует учитывать следующие положения: – Подк лючать прибор иск лючительно к безопасно малому напряжению и в обесточенном состоянии. Во избежание повреж дений и отказов...
  • Page 47 Reprint in full or in parts requires permission from S+S Regeltechnik GmbH. La reproduction des textes même partielle est uniquement autorisée après accord de la société S+S Regeltechnik GmbH. Перепечатка, в том числе в сокращенном виде, разрешается лишь с согласия S+S Regeltechnik GmbH.
  • Page 48 D G F r Busadresse, binärcodiert Bus address, binary coded Adresse du bus, code binaire Адресс шины, двоичный 0 0 0 0 0 0 0 1 0 0 1 1 0 0 1 1 0 1 1 0 0 1 0 1 1 0 0 1 0 1 1 1 1 1 0 0 1 0 0 1 0 0 0 0 0 0 1 0...

Table des Matières