6000-3880-0000-1XX 38800-2021 V100 02 ⁄ 2021
RPS - SD
®
AERASGARD
RFTM - PS - xx
AERASGARD
®
D
Bedienungs- und Montageanleitung
Multifunktionaler Raumfühler bzw. Messumformer
für Feuchte, Temperatur, Feinstaub (PM) und CO2 - Gehalt,
kalibrierfähig, mit aktivem ⁄ schaltendem Ausgang
G
Operating Instructions, Mounting & Installation
Multifunctional room sensor and measuring transducer
for humidity, temperature, fine dust (PM) and CO2 content,
calibratable, with active ⁄ switching output
F
Notice d'instruction
Sonde d'ambiance multifonctions, resp. convertisseur de mesure,
pour l'humidité, la température, les particules fines (PM) et teneur en CO2,
étalonnable, avec sortie active ⁄ de commutation
r
Руководство по монтажу и обслуживанию
Многофункциональный датчик для помещений или измерительный
преобразователь для измерения влажности, температуры,
содержания мелкой пыли (твердые частицы, ТЧ) и углекислого газа,
калибруемый, с активным ⁄ релейным выходом
S+S REGELTECHNIK GMBH
THURN-UND-TAXIS - STR. 22
90411 NÜRNBERG ⁄ GERMANY
FON +49 ( 0 ) 911 ⁄ 5 19 47- 0
mail@SplusS.de
www.SplusS.de
RPS - SD
RFTM - PS - CO2 - W
RFTM - PS - CO2 - W
mit Display
with display
avec écran
с дисплеем
CARTONS
ET EMBALLAGE
PAPIER À TRIER

Publicité

Table des Matières
loading

Sommaire des Matières pour S+S Regeltechnik AERASGARD RFTM-PS Serie

  • Page 1 преобразователь для измерения влажности, температуры, с дисплеем содержания мелкой пыли (твердые частицы, ТЧ) и углекислого газа, калибруемый, с активным ⁄ релейным выходом S+S REGELTECHNIK GMBH THURN-UND-TAXIS - STR. 22 90411 NÜRNBERG ⁄ GERMANY CARTONS FON +49 ( 0 ) 911 ⁄ 5 19 47- 0 ET EMBALLAGE mail@SplusS.de...
  • Page 2 D G F r RPS - SD ® AERASGARD   RFTM - PS - xx AERASGARD ®   Maßzeichnung Gehäuse Baldur 2 Dimensional drawing Housing Baldur 2 Plan coté boîtier Baldur 2 Габаритный чертеж Корпус Baldur 2 32.6...
  • Page 3: Technische Daten

    ® AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 Wartungsfreier Raumfühler AERASGARD ® RPS - SD mit aktivem Ausgang, im formschönen Kunststoffgehäuse mit Schnappdeckel, Unterteil mit 4-Loch -Befestigung, zur Erfassung des Feinstaub-Gehalts (0...500 µg/m ).
  • Page 4 ® AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 TECHNISCHE DATEN (Fortsetzung) Umgebungstemperatur: 0...+ 50 °C zulässige Luftfeuchte: 0...95 % r. H. (ohne Betauung) Einlaufzeit: ca. 1 Stunde Ansprechzeit: < 2 Minuten elektrischer Anschluss: 0,14 - 1,5 mm , über Schraubklemmen Gehäuse:...
  • Page 5: Dip-Schalter

    ® ® AERASGARD AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 Schaltbild RFTM - PS - CO2 - W Schaltbild RPS - SD Stecker Display 1 2 3 1 2 3 Ausgänge Feinstaub [ g/m 1 2 3 Temperatur [°C] 1 2 3 4 5 6 7 8 9...
  • Page 6 Montage und Inbetriebnahme ACHTUNG !  Die minimale CO2 - Konzentration von Außenluft beträgt in begrünten, industrie armen Gegenden ca. 350 ppm (Ausgangs spannung = 1,75 V bei MB = 0...2000 ppm bzw. 0,7 V bei MB = 0...5000 ppm). Der Gas austausch im Sensorelement erfolgt durch Diffusion. Je nach Konzentrationsänderung und Strömungs geschwindigkeit der Luft in Sensor umgebung kann die Reaktion des Gerätes auf die Konzentrationsänderung verzögert auftreten.
  • Page 7 Montage und Inbetriebnahme Inbetriebnahme Nach dem Einschalten des Gerätes erfolgen ein Selbsttest und die Temperierung. Dieser Vorgang dauert je nach Umgebungsbedingun gen 30 - 50 Minuten, in dieser Zeit weicht die ausgegebene Analog spannung vom tatsächlichen Messwert ab. Anschließend kann optional eine manuelle Kalibrierung durchgeführt werden. Dabei ist darauf zu achten, dass keine Schadstoffe den Kalibriervorgang beeinflussen und der Sensor bei Frischluft betrieben wird.
  • Page 8 Montage und Inbetriebnahme VERSORGUNGSSPANNUNG: Schaltbild Einzelbetrieb Als Verpolungsschutz der Betriebsspannung ist bei dieser Gerätevariante eine Einweggleichrichtung bzw. Verpolungschutzdiode integriert. Diese interne Einweggleichrichtung erlaubt auch den Betrieb mit AC-Versor- gungsspannung. Das Ausgangssignal ist mit einem Messgerät abzugreifen. Hierbei wird Schaltung die Ausgangssignal gegen das Nullpotenial (O V) der Eingangsspannung Versorgung mit ge messen! AC 24V~...
  • Page 9: Wichtige Hinweise

    Wichtige Hinweise – Dieses Gerät darf nur in schadstofffreier, nicht kondensierender Luft, ohne Über- oder Unterdruck am Sensorelement eingesetzt werden. – Bei Aussen- und Kanalfühlern schützt der Sinterfilter des Sensorelementes den Feuchtesensor vor eventuellen Staub belastungen. Dieser Filter sollte bei Verunreinigung ⁄ Verschmutzung regelmäßig gewartet werden. –...
  • Page 10: Technical Data

    ® AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 Maintenance-free room sensor AERASGARD ® RPS - SD with active output, in an elegant plastic housing with snap-on lid, base with 4-hole attach- ment, for detecting the fine dust content (0...500 µg/m ).
  • Page 11 ® AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 TECHNICAL DATA (continued) Ambient temperature: 0...+ 50 °C Permitted humidity: 0…95 % r. H. (non-precipitating air) Warm up time: approx. 1 hour Response time: < 2 minutes Electrical connection: 0.14 - 1.5 mm , via screw terminals...
  • Page 12 ® AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 Schematic diagram RFTM - PS - CO2 - W Schematic diagram RPS - SD Plug for display 1 2 3 1 2 3 Outputs fine dust [ g/m 1 2 3 temperature [°C] 1 2 3 4 5 6 7 8 9...
  • Page 13 Installation and Commissioning ATTENTION!  The minimum CO2 concentration of outdoor air amounts to approx. 350 ppm (output voltage = 1.75 V at MR = 0...2000 ppm or 0.7 V at MR = 0...5000 ppm) in leafy, hardly industrialised areas. Gas inter-exchange in the sensor element happens by diffusion. Depending on the changes to the concentration and the flow velocity of the air surrounding the sensor, the reaction of the device to the change of concentration may take place with a delay.
  • Page 14 Installation and Commissioning Putting in operation After switching on the device, a self-test and tempering period follows. This procedure takes 30 - 50 minutes,depending on the ambient conditions. During this time the output analogue voltage differs from the actual measured value. Manual calibration can then be performed as an option.
  • Page 15 Installation and Commissioning SUPPLY VOLTAGE : Connecting scheme Individual operation For operating voltage reverse polarity protection, a one-way rectifier or reverse polarity protection diode is integrated in this device variant. This internal one-way rectifier on AC supply voltage. The output signal is to be tapped by a measuring instrument. The output signal is measured her against zero potential (O V) of the input voltage! Circuitry When this device is operated on DC supply voltage, the operating...
  • Page 16 General notes – This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element. – On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor against potential dust exposure. In case of pollution ⁄...
  • Page 17: Caractéristiques Techniques

    ® AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 Sonde d’ambiance AERASGARD ® RPS - SD sans entretien avec sortie active, dans un boîtier plastique élégant avec couvercle emboîté, partie inférieure avec fixation à 4 trous, pour déterminer la teneur en particules fines (0...500 µg/m ).
  • Page 18 ® AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 CARAC TÉRISTIQUES TECHNIQUES (Suit e) Température ambiante : 0...+ 50 °C Humidité de l’air admissible : 0...95 % h.r. (sans condensation) Temps de démarrage : env. 1 heure Temps de réponse : <...
  • Page 19: Interrupteur Dip

    ® AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 Schéma de raccordement RFTM - PS - CO2 - W Schéma de raccordement RPS - SD Plug for display 1 2 3 1 2 3 Outputs fine dust [ g/m 1 2 3...
  • Page 20: Montage Et Mise En Service

    Montage et mise en service ATTENTION !  La teneur minimale en CO2 de l'air extérieur dans des régions vertes à faible degré d'industrialisation est de l'ordre 350 ppm (tension de sortie = 1,75 V à MB = 0...2000 ppm, resp. 0,7 V à MB = 0...5000 ppm). L'échange de gazdans l'élément capteur s'effectue par diffusion. En fonction de la variation de la concentration et de la vitesse d'écoulement de l'air dans l'environnement du capteur, la réaction de l'appareil à...
  • Page 21 Montage et mise en service Mise en service Après la mise en marche de l’appareil, celui-ci effectue un autocontrôle et l’équilibrage de température. En fonction des conditions d'environnement, cette opération dure entre 30 - 50 minutes, pendant ce temps la tension analogique émise diffère de la valeur de mesure réelle. Un calibrage manuel peut ensuite être effectué...
  • Page 22 Montage et mise en service TENSION D’ALIMENTATION : Schéma de raccordement individuel Cette variante d’appareil est dotée d’une protection contre l’inversion de polarité, c’.-à.-d. elle comprend un redressement demi-onde (diode de redresse ment). Grâce à cette diode de redressement intégrée, les appareils 0 -10 V peuvent également être alimentés en courant alternatif.
  • Page 23: Généralités

    Généralités – Cet appareil ne doit être utilisé que dans un air non pollué, sans risque de condensation, sans risque de surpression ou dépression sur l’élément sensible. – Dans le cas des sondes extérieures et des sondes pour montage en gaine, le filtre fritté de l’élément sensible protège la sonde d’humidité contre la pénétration des particules de poussières.
  • Page 24: Технические Данные

    ® AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 Не нуждающийся в техническом обслуживании датчик для помещений AERASGARD ® RPS - SD с активным выходом, в элегантном пластиковом корпусе с защелкивающейся крышкой и четырьмя отверстиями для крепления в нижней части, для измерения содержания мелкой пыли (0...500 мкг/м...
  • Page 25 ® AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 ТЕ ХНИЧЕСКИЕ Д АННЫЕ (прод олжение) Окружающая температура: 0...+50 °C Допустимая относительная влажность воздуха: 0...95 % (без конденсата) Время выхода на рабочий режим: прибл. 1 час Время срабатывания: <...
  • Page 26 ® AERASGARD RPS - SD ⁄ RFTM - PS - xx Rev. 2021 - V11 Схема подключения RFTM - PS - CO2 - W Схема подключения RPS - SD Plug for display 1 2 3 1 2 3 Outputs fine dust [ g/m 1 2 3 temperature [°C] 1 2 3 4 5 6 7 8 9...
  • Page 27: Монтаж И Ввод В Эксплуатацию

    Монтаж и ввод в эксплуатацию ВНИМАНИЕ!  Минимальная концентрация CO2 в наружном воздухе в озелененных районах с малым количеством промышленных объектов составляет прибл. 350 млн (выходное напряжение = 1,75 В при диапазоне измерения 0...2000 млн или 0,7 В при диапазоне измерения 0...5000 млн ). Газообмен в чувствительном элементе осуществляется благодаря диффузии. В зависимости от изменения концентрации и скорости потока воздуха вблизи...
  • Page 28 Монтаж и ввод в эксплуатацию Запуск в эксплуатацию После включения прибора начинается самотестирование и терморегулирование. Этот процесс длится от 30 до 50 минут в зависимости от условий окружающей среды; в это время выходное аналоговое напряжение отличается от измеренного значения. После этого можно дополнительно выполнить ручную калибровку. При этом следить за тем, чтобы...
  • Page 29 Монтаж и ввод в эксплуатацию НАПРЯЖЕНИЕ ПИТАНИЯ: Схема соединения Одиночное подключение В качестве защиты от неправильного подключения рабочего напряжения в данный вариант прибора интегрирован однополупериодный выпрямитель или диод защиты от напряжения обратной полярности. В случае приборов, рассчитанных на напряжение 0 – 10 В, этот встроенный выпрямитель...
  • Page 30 Указания к продуктам – Данный прибор допускается применять только в воздухе без конденсата и вредных веществ, при отсутствии пониженного или повышенного давления вблизи чувствительного элемента. – В случае датчиков для наружной и канальной установки защита чувствительного элемента датчика влажности от возможного скопления пыли обеспечивается...
  • Page 31 Reprint in full or in parts requires permission from S+S Regeltechnik GmbH. La reproduction des textes même partielle est uniquement autorisée après accord de la société S+S Regeltechnik GmbH. Перепечатка, в том числе в сокращенном виде, разрешается лишь с согласия S+S Regeltechnik GmbH.
  • Page 32 D G F r RPS - SD ® AERASGARD   RFTM - PS - xx AERASGARD ®  ...

Ce manuel est également adapté pour:

Aerasgard rps-sdAerasgard rftm-ps-co2-w

Table des Matières