Masquer les pouces Voir aussi pour RCO2-W:

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

D G F r
6000-3740-0000-1XX 37400-2021 V101 01 ⁄ 2021
RCO2 - W ⁄ RLQ - CO2 - W
®
AERASGARD
RFTM - ( LQ ) - CO2 - W ⁄ RTM - CO2 - SD
AERASGARD
®
D
Bedienungs- und Montageanleitung
Multifunktionaler Raumfühler bzw. Messumformer,
für Feuchte, Temperatur, Luftgüte (VOC) und CO2 - Gehalt,
kalibrierfähig, mit aktivem ⁄ schaltendem Ausgang
G
Operating Instructions, Mounting & Installation
Multifunctional room sensors and measuring transducers,
for humidity, temperature, air quality (VOC) and CO2 content,
calibratable, with active ⁄ switching output
F
Notice d'instruction
Sonde d'ambiance (transmetteur) multifonctionnelle,
pour l'humidité, la température, la qualité d'air (COV) et de teneur en CO2
étalonnable, avec sortie active ⁄ tout ou rien
r
Руководство по монтажу и обслуживанию
Мультифункциональный датчик для помещений ⁄ измерительный
преобразователь, для измерения влажности, температуры,
качества воздуха (VOC) и содержания CO2, калибруемый,
с активным ⁄ релейным выходом
S+S REGELTECHNIK GMBH
THURN-UND-TAXIS - STR. 22
90411 NÜRNBERG ⁄ GERMANY
FON +49 ( 0 ) 911 ⁄ 5 19 47- 0
mail@SplusS.de
www.SplusS.de
Edelstahlgehäuse
(optional auf Anfrage)
Stainless steel housing
(optionally available upon request)
Boîtier en acier inox
(en option sur demande)
Высококачественной стали
(опционально по запросу)
CARTONS
ET EMBALLAGE
PAPIER À TRIER

Publicité

Table des Matières
loading

Sommaire des Matières pour S+S Regeltechnik RCO2-W

  • Page 1 (optionally available upon request) Boîtier en acier inox (en option sur demande) Высококачественной стали (опционально по запросу) S+S REGELTECHNIK GMBH THURN-UND-TAXIS - STR. 22 90411 NÜRNBERG ⁄ GERMANY CARTONS FON +49 ( 0 ) 911 ⁄ 5 19 47- 0 ET EMBALLAGE mail@SplusS.de...
  • Page 2 D G F r RCO2 - W ⁄ RLQ - CO2 - W ® AERASGARD   RFTM - ( LQ ) - CO2 - W ⁄ RTM - CO2 - SD AERASGARD ®   Maßzeichnung Gehäuse Baldur 2 Dimensional drawing Housing Baldur 2 Plan coté...
  • Page 3: Technische Daten

    ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 Wartungsfreier Raumfühler AERASGARD ® RTM - CO2 - SD mit aktivem Ausgang, automatischer Kalibrierung, im formschönen Kunststoffgehäuse mit Schnappdeckel, zur Ermittlung des CO2-Gehalts der Luft (0...2000 ppm) und der Temperatur (0...+50°C).
  • Page 4 ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 TECHNISCHE DATEN (Fortsetzung) Umgebungstemperatur: 0...+ 50 °C zulässige Luftfeuchte: 0...95 % r. H. (ohne Betauung) Einlaufzeit: ca.
  • Page 5 ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 RFTM - LQ - CO2 - W RTM - CO2 - SD Schaltbild Schaltbild Sensor...
  • Page 6 Montage und Inbetriebnahme ACHTUNG !  Die minimale CO - Konzentration von Außenluft beträgt in begrünten, industrie armen Gegenden ca. 350 ppm (Ausgangs spannung = 1,75 V bei MB = 0...2000 ppm bzw. 0,7 V bei MB = 0...5000 ppm). Der Gas austausch im Sensorelement erfolgt durch Diffusion. Je nach Konzentrationsänderung und Strömungs geschwindigkeit der Luft in Sensor umgebung kann die Reaktion des Gerätes auf die Konzentrationsänderung verzögert auftreten.
  • Page 7 Montage und Inbetriebnahme Inbetriebnahme Nach dem Einschalten des Gerätes erfolgen ein Selbsttest und die Temperierung. Dieser Vorgang dauert je nach Umgebungsbedingun gen 30 - 50 Minuten, in dieser Zeit weicht die ausgegebene Analog spannung vom tatsächlichen Messwert ab. Anschließend kann optional eine manuelle Kalibrierung durchgeführt werden. Dabei ist darauf zu achten, dass keine Schadstoffe den Kalibriervorgang beeinflussen und der Sensor bei Frischluft betrieben wird.
  • Page 8 Montage und Inbetriebnahme VERSORGUNGSSPANNUNG: Schaltbild Einzelbetrieb Als Verpolungsschutz der Betriebsspannung ist bei dieser Gerätevariante eine Einweggleichrichtung bzw. Verpolungschutzdiode integriert. Diese interne Einweggleichrichtung erlaubt auch den Betrieb mit AC-Versorgungs- spannung. Das Ausgangssignal ist mit einem Messgerät abzugreifen. Hierbei wird Schaltung die Ausgangssignal gegen das Nullpotenial (O V) der Eingangsspannung Versorgung mit ge messen! AC 24V~...
  • Page 9: Wichtige Hinweise

    Wichtige Hinweise – Dieses Gerät darf nur in schadstofffreier, nicht kondensierender Luft, ohne Über- oder Unterdruck am Sensorelement eingesetzt werden. – Bei Aussen- und Kanalfühlern schützt der Sinterfilter des Sensorelementes den Feuchtesensor vor eventuellen Staub belastungen. Dieser Filter sollte bei Verunreinigung ⁄ Verschmutzung regelmäßig gewartet werden. –...
  • Page 10: Technical Data

    ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 Maintenance-free room sensor AERASGARD ® RTM - CO2 - SD with active output, automatic calibration, in an elegant plastic housing with snap-on lid, for determining the CO2 content of the air (0...2000 ppm) and the temperature (0...+50°C).
  • Page 11 ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 TECHNICAL DATA (continued) Ambient temperature: 0...+ 50 °C Permitted humidity: 0...95 % r. H. (non-precipitating air) Warm up time: approx.
  • Page 12 ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 RTM - CO2 - SD Schematic diagram RFTM - LQ - CO2 - W Schematic diagram Plug for sensor...
  • Page 13 Installation and Commissioning ATTENTION!  The minimum CO concentration of outdoor air amounts to approx. 350 ppm (output voltage = 1.75 V at MR = 0...2000 ppm or 0.7 V at MR = 0...5000 ppm) in leafy, hardly industrialised areas. Gas inter-exchange in the sensor element happens by diffusion. Depending on the changes to the concentration and the flow velocity of the air surrounding the sensor, the reaction of the device to the change of concentration may take place with a delay.
  • Page 14 Installation and Commissioning Putting in operation After switching on the device, a self-test and tempering period follows. This procedure takes 30 - 50 minutes,depending on the ambient conditions. During this time the output analogue voltage differs from the actual measured value. Manual calibration can then be performed as an option.
  • Page 15 Installation and Commissioning SUPPLY VOLTAGE : Connecting scheme Individual operation For operating voltage reverse polarity protection, a one-way rectifier or reverse polarity protection diode is integrated in this device variant. This internal one-way rectifier on AC supply voltage. The output signal is to be tapped by a measuring instrument. The output signal is measured her against zero potential (O V) of the input voltage! Circuitry When this device is operated on DC supply voltage , the operating voltage...
  • Page 16 General notes – This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element. – On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor against potential dust exposure. In case of pollution ⁄...
  • Page 17: Caractéristiques Techniques

    ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 Sonde d’ambiance AERASGARD ® RTM - CO2 - SD sans entretien avec sortie active, calibrage automatique, dans un boîtier plastique élégant avec couvercle emboîté, pour déterminer la teneur en CO2 dans l’air (0...2000 ppm) et la température (0...+50°C).
  • Page 18 ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 CARAC TÉRISTIQUES TECHNIQUES (Suite) Température ambiante : 0...+50 °C Humidité d’air admissible : 0...95 % h.r.
  • Page 19 ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 RTM - CO2 - SD Schéma de raccordement RFTM - LQ - CO2 - W Schéma de raccordement Plug for sensor...
  • Page 20: Montage Et Mise En Service

    Montage et mise en service ATTENTION !  La teneur minimale en CO de l'air extérieur dans des régions vertes à faible degré d'industrialisation est de l'ordre 350 ppm (tension de sortie = 1,75 V à MB = 0...2000 ppm, resp. 0,7 V à MB = 0...5000 ppm). L'échange de gazdans l'élément capteur s'effectue par diffusion. En fonction de la variation de la concentration et de la vitesse d'écoulement de l'air dans l'environnement du capteur, la réaction de l'appareil à...
  • Page 21 Montage et mise en service Mise en service Après la mise en marche de l’appareil, celui-ci effectue un autocontrôle et l’équilibrage de température. En fonction des conditions d'environnement, cette opération dure entre 30 - 50 minutes, pendant ce temps la tension analogique émise diffère de la valeur de mesure réelle. Un calibrage manuel peut ensuite être effectué...
  • Page 22 Montage et mise en service TENSION D’ALIMENTATION : Schéma de raccordement individuel Cette variante d’appareil est dotée d’une protection contre l’inversion de polarité, c’.-à.-d. elle comprend un redressement demi-onde (diode de redresse ment). Grâce à cette diode de redressement intégrée, les appareils 0 -10 V peuvent également être alimentés en courant alternatif.
  • Page 23: Généralités

    Généralités – Cet appareil ne doit être utilisé que dans un air non pollué, sans risque de condensation, sans risque de surpression ou dépression sur l’élément sensible. – Dans le cas des sondes extérieures et des sondes pour montage en gaine, le filtre fritté de l’élément sensible protège la sonde d’humidité contre la pénétration des particules de poussières.
  • Page 24: Технические Данные

    ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 Не нуждающийся в техническом обслуживании датчик для помещений AERASGARD ® RTM - CO2 - SD с активным выходом, автоматической калибровкой, в...
  • Page 25 ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 ТЕХНИЧЕСКИЕ Д АННЫЕ (прод олжение) Окружающая температура: 0 ...+50 °C Допустимая отн. влажность воздуха: 0...95 % отн. вл. (без конденсата) Время...
  • Page 26 ® AERASGARD RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD Rev. 2021 - V31 RTM - CO2 - SD Схема подключения RFTM - LQ - CO2 - W Схема...
  • Page 27: Монтаж И Ввод В Эксплуатацию

    Монтаж и ввод в эксплуатацию ВНИМАНИЕ!  Минимальная концентрация CO в наружном воздухе в озелененных районах с малым количеством промышленных объектов составляет прибл. 350 млн (выходное напряжение = 1,75 В при диапазоне измерения 0...2000 млн или 0,7 В при диапазоне измерения 0...5000 млн ). Газообмен в чувствительном элементе осуществляется благодаря диффузии. В зависимости от изменения концентрации и скорости потока воздуха вблизи...
  • Page 28 Монтаж и ввод в эксплуатацию Запуск в эксплуатацию После включения прибора начинается самотестирование и терморегулирование. Этот процесс длится от 30 до 50 минут в зависимости от условий окружающей среды; в это время выходное аналоговое напряжение отличается от измеренного значения. После этого можно дополнительно выполнить ручную калибровку. При этом следить за тем, чтобы...
  • Page 29 Монтаж и ввод в эксплуатацию НАПРЯЖЕНИЕ ПИТАНИЯ: Схема соединения Одиночное подключение В качестве защиты от неправильного подключения рабочего напряжения в данный вариант прибора интегрирован однополупериодный выпрямитель или диод защиты от напряжения обратной полярности. В случае приборов, рассчитанных на напряжение 0 – 10 В, этот встроенный выпрямитель допускает...
  • Page 30 Указания к продуктам – Данный прибор допускается применять только в воздухе без конденсата и вредных веществ, при отсутствии пониженного или повышенного давления вблизи чувствительного элемента. – В случае датчиков для наружной и канальной установки защита чувствительного элемента датчика влажности от возможного скопления пыли обеспечивается...
  • Page 31 Reprint in full or in parts requires permission from S+S Regeltechnik GmbH. La reproduction des textes même partielle est uniquement autorisée après accord de la société S+S Regeltechnik GmbH. Перепечатка, в том числе в сокращенном виде, разрешается лишь с согласия S+S Regeltechnik GmbH.
  • Page 32 D G F r RCO2 - W ⁄ RLQ - CO2 - W ® AERASGARD   RFTM - ( LQ ) - CO2 - W ⁄ RTM - CO2 - SD AERASGARD ®  ...

Table des Matières