SPECIFICATION
Capacity / VAC / kW
Steam pressure
Dimensions (inches / mm)
Weight empty/packaged/installed
with water (pounds / kilograms)
IP class
Electrode power cables
Power relays (amps)
Ground connection
Input water type
Conductivity range (microSiemens)
Water fill connection
Water fill - instant flow
Drain hose
Drain water temp F / C
Drain flow
Serial communication
Unit voltages
Electrical requirements
Max output
Steam hose
8" Steam manifold (standard)
GF-12502 air pressure switch
RMB35 room steam kit
Steam nozzle
GF-DPO30KIT
GF-DP045KIT
Copper tubing
Inline pre-filter
Condensate pump
Tab. 8.a

8. TECHNICAL SPECIFICATIONS

DESCRIPTION
4.9 lbs/hr (2.2 kg/h) / 115 VAC 1-phase 50-60 Hz / 1.86 kW
9.9 lbs/hr (4.5 kg/h) / 230 VAC 1-phase 50-60 Hz / 4.05 kW
3.81 in WC / 950 Pa (.137 PSI)
21" H x 13" W x 8.25" D / 533mm H x 343mm W x 210mm D
16 / 26 / 24 lbs. (7.3 / 12 / 11 kg)
IP20
AWG12
2 x 30
Screw
Potable water
125-1250 µS/cm
1/4" O.D. Compression
0.09 – 0.16 gpm (0.35 – 0.60 l/min)
¾" ID x 10 ft. drain hose supplied (19 mm ID)
< 140°F / < 60°C
Initial Max drain rate using ¼" OD supply tubing and full cylinder – approx 1.1 gallons for first 15
seconds of drain cycle (~4.4 gpm (13.2 l/min))
Initial Max drain rate using hose with ¾" BSP fitting – 6.3 gpm (23.8 l/min)
Average drain rate – 3.8 gpm (14.4 l/min) (measured over a one minute period starting with full
cylinder)
DS485
Primary 115 / 230 Volts AC / Control Wiring 12 Volts DC
Require AWG12 external power wires to electrical panel with a dedicated 20A
28.5 GPD max. If unit is not config.d (section 4.4) then default setting from factory is 20.9 GPD at
230V
6' blue steam hose ID 7/8" (22mm), OD 1 ¼" (30mm), (GFI #7525)
8" steam manifold supplied with duct mounting kit
OPTIONAL
Actuated by positive, negative or differential pressure of .05" W. C. or more (GFI #7021)
230V Includes room blower assembly and grille package (GFI #7660)
Optional accessory can be used for bottom duct installation (GFI #7500 / CGF#GF-20-1)
Optional accessory 12" length steam distribution manifold (GFI #7521)
Optional accessory 17.5" length steam distribution manifold (GFI #7522)
FIELD SUPPLIED
OD 3/4" to fit ID of blue steam hose
Any activated carbon element and particulate element rated for 5 micron or less and min 25 GPM
3 gpm min. flow at 0 head and 1 gallon reservoir min. The technician is responsible for selecting the
appropriate condensate pump for the installation
30
NOTES
On board
No demineralized or softened water
Adapter to 3/4" BSP
From bottom of unit
Drain tempering device