During the cleaning, the electrodes are powered and water
in the cylinder rises until it touches the high-level sensor or
reaches the high current limit; whichever comes first. After
either of the events is detected, the cylinder is fully discharged
with the electrodes un-powered (the drain pump and the drain
tempering valve are activated for 3 minutes). It is recommended
that two cleanings are performed when starting a new steam
unit. After the cleaning ends, the humidifier begins its regular
function. When starting the unit with a new or empty cylinder,
it may take a significant amount of time (hours) for the unit
to build up enough mineral concentration to reach rated
capacity. This time can be shortened by the addition of a
teaspoon of salt or ¼ of an antacid tablet through the steam
outlet on top of the cylinder.
Resetting the cylinder hour counter:
1.
Switch the unit off. While pressing and holding both the
"RESET/SEL" and  "DRAIN/ENT"  buttons, then switch the
unit on. Continue to hold both buttons until the wrench
symbol starts to blink, and then release both buttons.
2.
Press and hold the "RESET/SEL" button until the value is
03 as shown on the display.
3.
Press "drain" for a minimum of 1 second to confirm. The
hour counter will be reset once the unit resumes normal
operation.