How To Connect; Power Cord Connection; Electrical Connection; Direct Connection - GE Appliances Zoneline 4100 Manuel D'utilisation Et Instructions D'installation

Table des Matières

Publicité

230/208 VOLT ELECTRICAL CONNECTION OPTIONS

HOW TO CONNECT

1. Remove the room cabinet.
2. Connect to electrical power.
3. Review the following steps for applicable supply
voltages.
4. Reinstall the room cabinet.
POWER CORD
CONNECTION
A power supply kit with LCDI must be used to supply power
to the Zoneline unit. The appropriate kit is determined by
the voltage, the means of electrical connection and
the amperage of the branch circuit.
Appearance may vary.
Power supply kit
Connections of 208 or 230-volt circuits may be with a
power supply kit or a junction box kit.
All wiring, including installation of the receptacle, must
be in accordance with the NEC and local codes,
ordinances and regulations. Codes require the use of
an arc fault or leakage current detection device on the
power cord except direct connect. Be sure to select the
correct cord for your installation.
Perpendicular
Tandem
15 Amp.
20 Amp.
230/208-volt receptacle configuration.
Branch Circuit and
Unit Amperage Rating
15
20
30
*Not approved for use on 7000 BTU models.
Installation Instructions
Large Tandem
30 Amp.
Proper GE Power Cord
with LCDI Device
RAK3153A
RAK3203A
RAK3303*
Power cords may include an arc fault interruption
or a leakage current detection interruption device.
A test and reset button is provided on the plug case
or the inline case. The device should be tested on
a periodic basis by first pressing the TEST button
and then the RESET button. If the TEST button does
not trip or if the RESET button will not stay engaged,
discontinue use of the Zoneline and contact a
qualified service technician.
ELECTRICAL SUBBASE
CONNECTION
230/208-volt models may be installed using one
of the following electrical subbases:
Branch Circuit and
Unit Amperage Rating
15
20
30
*Not approved for use on 7000 BTU models.
Electrical subbases provide an enclosure for direct
connection or enclosed receptacles. The subbase kit
includes the power cord.
The instructions provided with the selected subbase kit
must be carefully followed. It is the responsibility of the
installer to ensure the connection of components is done
in accordance with these instructions and all electrical
codes.

DIRECT CONNECTION

Order the following Kit for 230/208-volt direct
connection as required:
Branch Circuit and
Unit Amperage Rating
15
20
30
*Not approved for use on 7000 BTU models.
Skip to the "MAKE ELECTRICAL CONNECTION TO THE UNIT"
section.
13
Proper GE
Subbase Kit
RAK204D15P
RAK204D20P
RAK204D30P*
Power Supply
Power
Accessory
Supply Kit
RAK4002A
RAK4157
RAK4002A
RAK4207
RAK4002A
RAK4307*