Device Informa-
The device is used to display settings relevant to a power supply company. The displayed
tion
values depend on the respective country setup or device-specific inverter settings.
Display range
General:
Country-specific set-
ting:
MPP Tracker:
Monitoring the grid:
Voltage limits:
Frequency limits:
Q-mode:
AC power limits:
AC voltage derating:
General / Country-specific setting / MPP tracker / Grid monitor-
ing / Grid voltage limits / Grid frequency limits / Q-mode / AC
power limit / AC voltage derating
Device type
Fam.
Setup
Country setup
Version
Country setup version
Group
Inverter software update group
Tracker 1
GMTi
Startup time of the inverter in s
GMTr
Restart time in s after a grid error
ULL
Grid voltage average value over 10 minutes in V
LLTrip
Detection time for long-term voltage monitoring
UILmax
Upper inner grid voltage value in V
UILmin
Lower inner grid voltage value in V
FILmaw
Upper inner grid frequency value in Hz
FILmin
Lower inner grid frequency value in Hz
Current power factor cos phi
(e.g., constant cos(phi) / constant Q / Q(U) characteristic / etc.)
Max. P AC
manual power reduction
Status
ON / OFF voltage-dependent power reduction
GVDPRe
Threshold from which the voltage-dependent power reduction
begins
GVDPRv
Reduction gradient used to reduce the power, e.g.: 10% per volt
above the GVDPRe threshold.
Message
Activates the dispatch of an info message via Fronius Solar Net
33