7. Starting, operation
7. Starting, operation
Required tools
Wrench (flats 27 or flats 41), screw driver
Diaphragm test for your safety
It is necessary that before starting the pressure transmitter you test the diaphragm visually, as
this is a safety-relevant component.
WARNING!
Pay attention to any liquid leaking out, for this points to a diaphragm damage.
■
Check the diaphragm visually for any damage (E-11).
■
Use the pressure transmitter only if the diaphragm is undamaged.
■
Use the pressure transmitter only if it is in a faultless condition as far as the
■
safety-relevant features are concerned.
Mechanical connection
Make sure the ventilation
port remains open to
atmospharic pressure.
Use only to secure
transmitter while installing
electrical conduit
Use to install the transmit-
ter process connection
max. 50 Nm / 442 lbf
If there is no serial number on the product label, the number on the hexagon will apply.
8
Product label (example)
Transmitter E-10
0 ... 10 bar
4 ... 20 mA
10 ... 30 V
brown+ green-
P#
0639080
brown S+ green GND
Code E-10-XXXXXXX
WIKA Alexander Wiegand SE & Co. KG 63911 Klingenberg
Pressure range
Signal
Power Supply
P #:
Product No.
PIN assignment
WIKA operating instructions, models E-10, E-11
US
Type 4
Explosionproof for
CLI, DIV.1, GRP A,B,C,D
CLII, DIV.1, GRP E, F, G; CL III
Ta < 60 °C, T6, Ta < 105 °C, T4
factory sealed,
conduit seal not required
CSA Single Seal ANSI/ISA12.27.01
-30 °C < Tprocess < 100 °C
3D
Made in Germany
Coded
manufacture
date