7 Drive Logic Parameters
15.02 (DRIVE MODE)
15.05 (USED FEX TYPE)
15.06
(FIELD CONTRL MODE)
15.16
(OPER MODE SELECT)
15.22 (COMMAND SEL)
8 Motor Nominal Values
41.03
(MOT 1 NOM FLD CUR)
41.19 (INT EMF REF)
(
)
=
41
.
19
INT
EMF
REF
100
9 Measurement Settings
42.06
(NOM SUPPLY VOLTAGE)
(only A6 / A7 / C4 modules)
Parameters 42.07 to 42.11 should only be set for converters
size A6 / A7 / C4 (1900 A ... 5200 A).
42.07
(S CONV NOM CURR)
42.08
(S CONV NOM VOLT)
42.09
(S MAX BRIDGE TEMP)
42.10
(S CONVERTER TYPE)
42.11
(S QUADRANT TYPE)
Save the new data with 15.02 (DRIVE MODE) = 22. After
successful saving 15.02 is automatically set back to zero.
10 Speed Measurement
50.01 (SPEED SCALING) = maximum motor speed; since
this short commissioning is only for EMF control the maxi-
mum speed is equal to the base speed of the motor.
Set parameters 20.01 (MINIMUM SPEED), 20.02 (MAXI-
MUM SPEED) and 20.11 (OVERSPEED LIMIT) according-
ly
50.03 (SPEED FB SEL)
= 2; NORMAL MODE (de-
fault)
= 1; SDCS-FEX-1
2; SDCS-FEX-2A, DCF
503A/504A or DCF 60x
for more options see Soft-
ware Description
= FIX (default)
= 6P SINGLE (default)
= LOCAL I/O
= rated motor field current
in A
= internal EMF reference in
%, to calculate use follow-
ing formula:
(
99
.
02
MOTOR
NOM
VOLTAGE
%
*
(
42
.
06
NOM
SUPPLY
= rated supply (incoming)
voltage in V
= rated converter current in
A; this is the DC current,
see rating plate I2
= rated converter coding
voltage in V; set it to the
value how the SDCS-PIN-
5x board is cut (see
Technical Data chapter 5 )
= 45°C; trip level of convert-
er temperature in degree
Celsius
= MANUAL SET
= 1 QUADRANT if
DCS 601 xxxx,
2 QUADRANT if
DCS 602 xxxx.
= CALC BY EMF (default)
I 16
3ADW000179R0100_DCS600_QuickGuide_edisf_a
97.01 (DEVICE NAME)
98.02 (COMM MODULE)
98.08 (IO BOARD CONFIG) = NO I/O BOARD
99.02
(MOTOR NOM VOLTAGE)
)
)
VOLT
99.03
(MOTOR NOM CURRENT)
99.05
(MOTOR NOM SPEED)
ON via DriveWindow. Please wait a few moments. Dur-
ing this time the phase sequence of the mains is checked.
In case F 38 (PHAS SEQU) appears change parameter
42.01 (MAINS PHASE ORDER).
For A6 / A7 / C4 modules the turning direction of the three
phase fan has to be checked.
Get rid of all faults and alarms if any.
START and give a speed reference via DriveWindow.
The motor should now turn with the desired speed.
STOP and OFF via DriveWindow.
15 Autotuning of armature current controller
• 15.02 (DRIVE MODE) = 3
• ON via DriveWindow.
• START via DriveWindow within the next 20 seconds.
• After a successful autotuning the parameter 15.02 is set back
to 0. In case of an error parameter 15.02 is set to -1 (see
Software Description chapter 25 ).
• OFF via DriveWindow.
16 Autotuning of field current controller 1
• ON via DriveWindow.
• 15.02 (DRIVE MODE) = 5
• After a successful autotuning the parameter 15.02 is set back
to 0. In case of an error parameter 15.02 is set to -1 (see
Software Description chapter 2 5).
• OFF via DriveWindow.
11 Drive
= name of the drive; is shown
in DriveWindow
12 Option Modules
= NO
IOB2; only SDCS-IOB-2
present
IOB3; only SDCS-IOB-3
present
IOB2+3; SDCS-IOB-2 and
SDCS-IOB-3 present
for more options see Soft-
ware Description
13 Start-up Data
= rated motor voltage (see
motor rating plate)
= rated motor current (see
motor rating plate)
= motor base speed (field
weakening point); since this
short commissioning is only
for EMF control the maxi-
mum speed is equal to the
base speed of the motor.
14 Turn the motor
taken from/for further information:
Operating instructions
3ADW000080