Application; Personnel Qualification; Product Service Life - Helios MiniVent M1 150 N C Notice De Montage Et D'utilisation

Mini ventilateur
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operation Instructions
EN
m
DANGER
MiniVent M1/150 N / C
• When using a vented fire place (chimney) in a ventilated room, there
must be sufficient supply air for all operating conditions (consult chim-
ney sweep).
The current locally applicable regulations and laws must be observed!
1.3

Application

– Normal use:
The MiniVent M1/150 N / C mini fans are suitable for conveying normal or slightly dusty (particle size < 10 µm), less ag-
gressive and humid air, in moderate climates and in the range of their performance curves, see Helios sales documents
/ internet. Operation is only admissible with fixed installation within buildings. The maximum admissible media and
ambient temperature is 40 °C. MiniVent M1/150 N / C mini fans correspond to protection category IP45, protection
class II and may be installed in area 1 wet rooms according to VDE 0100 part 701.
– Reasonably foreseeable misuse:
The fans are not suitable for operation under difficult conditions, such as high levels of humidity, aggressive media, long
standstill periods, heavy contamination, excessive loads due to climatic, technical or electronic influences. The same
applies for the mobile use of fans (vehicles, aircraft, ships, etc.). Usage under these conditions is only possible with
release approval from Helios, as the standard version is not suitable in this case.
– Improper, prohibited use:
Any use other than the intended use is not permitted! The conveying of solid matter or solid matter content > 10µm
in air and liquid is not permitted. Transport media, which affect the materials of the fan, and abrasive media are not
permitted. Use in explosive atmospheres is not permitted!
1.4

Personnel qualification

m
DANGER!
The electrical connection and start-up as well as installation, servicing and maintenance of the fan must only be carried
out by qualified electricians.
MiniVent M1/150 N / C mini fans can be used by children over the age of 8 as well as persons with physical, sensory, or
mental disabilities or lack of experience and knowledge, if they are supervised or instructed with regard to the safe use of the
unit and they understand the resulting risks. Children must not play with the unit. Cleaning or user maintenance must not be
carried out by unsupervised children.
1.5

Product service life

This unit is designed for a product service life of at least 40,000 h, in case of S1 operation with maximum power in the
maximum permissible ambient temperature.
2

Publicité

Table des Matières
loading

Table des Matières