Check Water Flow - Elco R600 Notice D'installation Et D'emploi

Table des Matières
Les langues disponibles
  • FR

Les langues disponibles

Commissioning

Check water flow

Check water flow
The water flow through the boiler can
be checked with two different methods
shown below.
∆T measurement
Check the temperature difference over
the boiler (∆T flow-return) when the
boiler is running on 100% load. The
nominal ∆T is 20K and must be at least
between 15K and 25K for secure boiler
operation. An indication of the actual
flow rate can be found with the follo-
wing calculation (see table below for
nominal data):
q
= (∆T
/ ∆T
actual
nominal
measured
∆p measurement
Check the pressure difference over the
boiler (∆p flow-return) when the boiler
pump is running (burner on is not requi-
red). The nominal ∆p for each boiler
type can be found in the table below,
actual ∆p must be within:
0.35*Δp
≤ ∆P ≤ 1.75*∆p
nom
indication of the actual flow rate can be
found with the following calculation (see
table below for nominal data):
q
= √(∆p
/ ∆p
actual
measured
nominal
Nominal flow rate
∆T at nominal flow rate
∆p at nominal flow rate
3
) * q
[m
/h]
nominal
. An
nom
3
) * q
[m
/h]
nominal
Water flow data
R601
3
[m
/h]
6.1
[ºC]
[kPa]
10
R602
R603
R604
8.1
10.2
12.2
20
18
28
15
R605
R606
R607
16.3
20.4
23.1
27
42
55
17