Automatic (Switching Mode) - Niko 350-34001 Manuel Technique

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Channel 2
This parameter allows you to select and activate the functions of channel 2.
Automatic
Lux value switch
Alarm mode
Constant light control
Disable
Channel 3
This parameter allows you to select and activate the functions of channel 3.
Automatic
Lux value switch
Alarm mode
Constant light control
Disable
Channel 4 (HVAC only)
This parameter allows you to select and activate the HVAC channel.
Default value: Disable
Disable
Enable

4.4. Automatic (Switching mode)

Parameter
Description
Switch-on lux adjustment
With this parameter, you can activate the switch-on brightness: the detector will switch on when motion is detected and there is not enough brightness.
(0=always on, 2000, lux
# lux (0=always ON, 2000 lux max)
max)
PM350-34x0x_EN
1. When in Automatic mode, the load is activated automatically when motion is detected and the ambient light level is below the lux setting
value. When no motion is detected and the switch-off delay time has expired, the load will go off automatically.
2. The switching output for the channel is locked with an ON telegram and unlocked with an OFF telegram.
3. The alarm function can be set to react differently or identically at switch ON and switch OFF.
In lux value switch mode, the twilight switch sends an ON telegram if the threshold value is not reached during the entire switching time. An OFF
telegram is sent if the threshold value is exceeded during the entire switching time.
1. The number of motions detected within a specific time span can be customised as a condition for triggering an alarm. An alarm is triggered
if a continuous number of moving objects are detected.
2. The alarm function can be set to react differently identically at switch ON and switch OFF.
3. The switching output for the channel is locked with an ON telegram and unlocked with an OFF telegram.
1. In constant light control mode, the detector monitors changes in the ambient light level and matches the dimming level of the lighting to the
lux setting value.
2. The switching output for the channel is locked with an ON telegram and unlocked with an OFF telegram.
Channel 2 is disabled.
1. When in Automatic mode, the load will go on automatically when motion is detected and the ambient light level is below the lux setting value.
When no motion is detected and the delay time has expired, the load will go off automatically.
2. The switching output for the channel is locked with an ON telegram and unlocked with an OFF telegram.
3. The alarm function can be set to react differently or identically at switch ON and switch OFF.
In lux value switch mode, the twilight switch sends an ON telegram if the threshold value is not reached during the entire switching time. An OFF
telegram is sent if the threshold value is exceeded during the entire switching time.
1. The number of motions detected within a specific time span can be customised as a condition for triggering an alarm. An alarm is triggered if
a continuous number of moving objects are detected.
2. The alarm function can be set to react differently or identically at switch ON and switch OFF.
3. The switching output for the channel is locked with an ON telegram and unlocked with an OFF telegram.
1. In constant light control mode, the detector monitors changes in the ambient light level and matches the dimming level of the lighting to the
lux setting value.
2. The switching output for the channel is locked with an ON telegram and unlocked with an OFF telegram.
Channel 3 is disabled.
The HVAC channel is disabled
The HVAC channel is enabled.
1. When in HVAC mode, an ON telegram is sent when a presence is detected.
If no presence is detected, an OFF telegram is sent, depending on the switch-off time.
2. The switching output for the HVAC channel is locked with an ON telegram and unlocked with an OFF telegram.
3. The HVAC function can be set to react differently or identically at switch ON and switch OFF.
If the lux level remains below this value, the detector will switch on.
350-34001/350-34002/350-340X3/350-340X4/350-34902
5
EN

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

350-34002350-340x3350-340x4350-34902

Table des Matières