DHW 300 - DHW 300+
Menu block
Menu item
(only visible for devices with additional heat exchanger and OFF or Sol selected)
Solar
Selection
Switch-on difference
Switch-off difference
Max. cylinder temp.
Max. collector temp.
(only visible for devices with additional heat exchanger and OFF or Bivalent selected)
2nd heat genera-
tor
Selection
Bivalence temperature
Photovoltaic
Electric heater
Set temperature
Information
Operating status
Runtimes
EN-10
Parameter
Value
Days
Su ... Mo
Mo - Fr
Sa - Su
Mo - Su
Off
Bivalent
Sol
6 K ... 8 K ... 10 K
2 K ... 4 K ... 6 K
60 °C ... 65 °C ... 85 °C
125 °C ... 130 °C ... 135 °C Sets the maximum permissible temperature on the collector
Off
Bivalent
Sol
-8 °C ... 10 °C ... 15 °C
Yes
No
35 °C ... 45 °C ... 60 °C
Cylinder top
Cylinder bottom
Air inlet
Collector temp.
Current setpoint
Defrost sensor
Fan
Compressor
Electric heater
Power
Operating mode
Unit
Fan
Compressor
Electric heater
451905.66.01 · FD 9511
Description
Sets the weekday / block of days on which the lower should be
activated
Choice of additional heat source
Off: (no add. heat source)
Bivalent: 2nd heat generator, e.g. oil, gas or wood boiler
Sol: Thermal solar energy system
Sets the temperature difference between the collector and cyl-
inder temperature at which the solar pump should be switched
on
Sets the temperature difference between the collector and cyl-
inder temperature at which the solar pump should be switched
off
Sets the maximum cylinder temperature that is permissible
when solar gain is available
Choice of additional heat source
Off: (no add. heat source)
Bivalent: 2nd heat generator, e.g. oil, gas or wood boiler
Sol: Thermal solar energy system
Limit temperature for the 2nd heat generator. The heat pump
is blocked below this temperature
Activates the electric heater (parallel to the heat pump) in pho-
tovoltaic mode
Entry of the domestic hot water setpoint, which is active when
photovoltaic inlet is connected. The increased setpoint is also
active if the air intake temperature does not allow the heat
pump to operate. In this case, the request is processed with
the electric heating element or, where present, the 2nd heat
generator.
Display of the cylinder temperature top (R3)
Display of the cylinder temperature bottom (R5)
Display of the air temperature (R1)
Display of the collector temperature (R13 only on models with
additional heat exchanger and Sol selected as 2nd heat gener-
ator)
Displays the current domestic hot water setpoint
Display the defrost (only on models with defrost)
Shows the switching status of the fan
Shows the switching status of the compressor
Shows the switching status of the electric heater
Shows the calculated power consumption of the device
Displays the current operating mode
Displays the operating hours
Shows the runtime of the fan
Shows the runtime of the compressor
Shows the runtime of the electric heater