BMF 203K-H- _ _ -C-A _ -... / BMF 235K-H- _ _ -C-A _ -...
Magnetic Field Sensors
7
IO-Link (continued)
7.5.2
Teach-in procedures
General information
Setpoint 2 (SP2) as per Smart Sensor profile is not
supported for this sensor and is always 0x0000.
In Single Value Teach both teach points TP1 and TP2
are taught at the same time and with the same value
(the status bits are therefore not supported).
Prerequisite
The sensor is mounted, aligned, and in IO-Link operation.
Teach-in
1. Move the cylinder to the desired position
2. Select the teach-in channel as follows:
Remarks
BDC1 (Standard)
BDC1...BDC8
All BDC
3. Start teach-in: Send system command 0x41 to the
sensor.
Remarks
Single Value Teach
4. Confirm teach-in: Send system command 0x40 to the
sensor.
Remarks
Teach Apply
5. Check whether teach-in was successful: read out the
teach-in status
Remarks
Teach-In Status = SP1 SUCCESS
Teach-In Status = ERROR
Setting switchpoint width.
The switchpoint width can be adjusted for each individual
switchpoint using the Switchpoint Width parameter:
Default setting: 5
Reduce switchpoint width: < 5 (Minimum = 1)
Expand switchpoint width: > 5 (Maximum = 10)
www.balluff.com
Index
0x003A (58)
Index
0x0002 (2)
Index
0x0002 (2)
Index
Access
0x003B (59)
R
Access
W
0x01...0x08 (1...8)
Access
W
Access
W
Values
Result
0x01 (1)
Teach-in completed successfully
0x07 (7)
Return to step 2
english
Values
0x00 (0)
0xFF (255)
Values
0x41 (65)
Values
0x40 (64)
19