Explanation display settings (DIS)
coLr
Colour configuration of the display
rEd = Display always red
GrEn = Display always green
r1ou = Display red in case of switched output OUT1
G1ou = Display green in case of switched output OUT1
r2ou = Display red in case of switched output OUT2
G2ou = Display green in case of switched output OUT2
diS
Update rate and orientation of the display
d1 = update of the measured values every 50 ms�
d2 = update of the measured values every 200 ms�
d3 = update of the measured values every 600 ms�
rd1, rd2, rd3 = display as for d1, d2, d3; rotated by 180°.
OFF = the measured value display is deactivated in the Run mode�
SELd
Standard display: flow or medium temperature

9 Set-up

After power on and expiry of the power-on delay time, the unit is in the normal
operating mode� It carries out its measurement and evaluation functions and
generates output signals according to the set parameters�
During the start up delay time the outputs are switched as programmed:
- ON with normally open function (Hno / Fno)
- OFF with normally closed function (Hnc / Fnc)
- OFF for frequency output (FRQ)
- 20 mA for current output (I)
UK
67