10.2.9 Carry out the remote calibration
► Select [ou2 ] and set [tch]�
1� High-flow adjustment:
► Apply the operating voltage to pin 2 for 5 to 10 s�
2� Low-flow adjustment:
► Apply the operating voltage to pin 2 for 10 to 15 s�
> OUT2 high for 2 s: adjustment successful�
> OUT2 high for 1 s: adjustment failed. ► Repeat the adjustment.
10.3 Settings for temperature monitoring
10.3.1 Configure the limit value monitoring for temperature for OUT2
► Select [SEL2] and set TEMP�
► Select [ou2] and set the switching function: Hno, Hnc, Fno or Fnc
1� When the hysteresis function is selected:
► Select [SP2] and set the value at which the output switches�
► Select [rP2] and set the value at which the output is reset�
2� When the window function is selected:
► Select [FH2] and set the upper limit value of the window�
► Select [FL2] and set the lower limit value of the window�
10.3.2 Configure the frequency signal for temperature for OUT2
► Select [SEL2] and set TEMP�
► Select [ou2] and set FRQ�
► Select [FSP2] and set the lower temperature value at which 0 Hz is
provided�
► Select [FEP2] and set the upper temperature value at which the frequen-
cy set in FrP2 is provided�
► Select [FrP2] and set the frequency: 100 Hz���1000 Hz�
10.3.3 Configure the analogue output for temperature for OUT2
► Select [SEL2] and set TEMP�
► Select [ou2] and set the function:
I = temperature-proportional current signal 4...20 mA
► Select [ASP2] and set the temperature value at which the output signal
is 4 mA�
► Select [AEP2] and set the temperature value at which the output signal
is 20 mA�