Before Installation - Burkert 6212 Manuel D'utilisation

Masquer les pouces Voir aussi pour 6212:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7.
insTallaTiOn
7.1.
safety instructions
Danger!
Risk of injury from high pressure in the equipment!
Before loosening the pipes and valves, turn off the
pressure and vent the pipes.
Risk of injury due to electrical shock!
Before reaching into the device or the equipment,
switch off the power supply and secure to prevent
reactivation!
Observe applicable accident prevention and safety
regulations for electrical equipment!
Warning!
Risk of injury from improper installation!
Installation may be carried out by authorized techni-
cians only and with the appropriate tools!
Risk of injury from unintentional activation of the
system and an uncontrolled restart!
Secure system from unintentional activation.
Following assembly, ensure a controlled restart.
english
16
7.4.
electrical connection of the
cable plug
Danger!
Risk of injury due to electrical shock!
Before reaching into the device or the equipment,
switch off the power supply and secure to prevent
reactivation!
Observe applicable accident prevention and safety
regulations for electrical equipment!
If the protective conductor is not connected, there is
a risk of electric shock!
Always connect protective conductor.
Check electrical continuity between coil and housing.
Seal
Authorised cable plug e.g. Type 2506
or other suitable cable plug in accor-
dance with DIN ISO 175301-803
Form C
Fig. 3:
Electrical connection of the cable plug
english
18
max. 0.4 Nm
7.2.

before installation

Installation position:
Installation can be in any position.
Preferably: Actuator upright.
Prior to installation check pipelines for dirt and, if required,
clean.
Dirt filter: To ensure that the solenoid valve functions reliably,
a dirt filter (≤ 500 µm) must be installed in front of the valve
inlet.
7.3.
installation
Hold the device with a suitable tool (open-end wrench)
on the housing and screw into the pipeline.
note!
Caution risk of breakage!
Do not use the coil as a lifting arm.
Observe direction of flow:
The arrow on the housing indicates the direction of flow
(no function in opposite flow direction)!
Note the voltage and current type as specified on
the rating plate.
Tighten cable plug (for permitted types see data sheet),
observing max. torque 0.4 Nm.
Check that seal is fitted correctly.
Connect protective conductor and check electrical
continuity between coil and housing.
Type 6212
english
17
english
19

Publicité