10. Assembly for actuation from right

Important!

• Prior to the assembly process, flush the pipework in accordance with DIN 1988.
• Mount the emergency shower in accordance with EN 15154 Part 1.
The manual actuator of the emergency shower can be plugged.
To protect the tiles, use masking tape when marking and drilling. Drill at low speed.
Depending on the composition of the wall, special wall plugs may have to be used
(to be provided by the customer).
For a door leaf width from 1 m, check whether the door frame obstructs the
assembly of the pull rod or wall support.
10.1 Door leaf width up to 1 m:
Align the wall panel (a) centrally above the door, 2310 ± 100 mm above the finished
floor in accordance with the water intake, and mark the drill holes.
10.2 Align the wall support (b) in accordance with the dimensions and mark the drill holes.
* Without the extension for the coupling rod (with the extension: +300 mm).
Alternatively, use the drilling template.
If using the extension for the coupling rod, do not use the provided drilling template.
Important!
To assemble the system for actuation on the right, use the indicated drill holes.
10.3 Drill in accordance with these markings.
10.4 Insert the wall plugs.
10.5 Screw on the wall plate (a) and the wall support (b).
10.6 Dismantle the fork head (d) from the valve lever (c).
10.7 Screw in the closed ball valve as far as possible, creating a seal and bringing it into
position as follows:
– The valve axis must point downwards (and not to the ceiling).
– The pivot motion of the valve lever must be aligned so that it is parallel to the
floor.
10.8 Secure the ball valve (f) with the two grub screws (e).
10.9 Mount the wall bearing linkage.
g: Rubber
h: Steel
10.10 Screw the fork head (d) to the coupling rod (j).
10.11 Mount the fork head (d) with the coupling rod to the valve lever (c).
10.12 Place the wall support (k) onto the guide (m) on the manual actuator and secure with
the grub screw (l).
10.13 Place the valve lever into the "close" position.
A: Closed
B: Open