Sensor Adjustment
Remove the wall plate. Remove the button cap by firmly squeezing together the top sides of the button assembly. Gently pull it away
from the unit.
When the adjustments are completed, replace the button cap by inserting its hinges into the tabs on the main unit and then squeezing
the top of the button while pressing it into the unit. Reinstall the cover plate.
PW-200 shown.
PW-100 has a
single button.
Light Level Adjustment
The light level can be set with loads ON or OFF. To enable light level control and set the threshold: 1) Make sure the room is lit
appropriately. 2) Put the sensor into TEST mode (see Time Delay switches). You have 5 minutes to complete the procedure. 3) Press
and hold the ON/OFF button (Relay 1 button on the PW-200) for 3 seconds, until you hear a beep. 4) Step away from the sensor. After
25 seconds a beep sounds, indicating that the threshold level is set. This threshold is retained, even if power is lost, until it is re-set or
disabled. In the PW-200, light level control only affects Relay 2.
To disable light level control, press and hold the Relay 1 button for 7 seconds, until a double beep tone sounds.
Reset to Default
Use the DIP Switch Settings tables to return features to factory settings. To reset the PW, press and hold the Relay 1 button for 10
seconds, until a triple beep sounds. This resets the sensor and disables light level control (the brightest ambient light will not hold the
light OFF).
10 minutes
15 minutes
20 minutes
25 minutes
30 minutes
Walk-Through
Service bypasses occupancy
& light level functions. Control the
load manually using ON/OFF button.
Button
Hinges

DIP SWITCH SETTINGS

1 2 3
Time Delay
Test/20 min
5 minutes
Service
4
Enabled
Disabled
ADJUSTMENTS
Tabs
Relay 1 Mode
Time
Visible
Delay
Alerts
ON
1
2
3
4
5
6
7
8
Walk-Through
Audible Alerts
PIR Sensitivity
5
PIR Sensitivity
Low, 50%
High
6
Visible Alert
Enabled
Disabled
=ON
=OFF
4
ON/OFF
Buttons
Relay 1
Relay 2
DIP Switches
Detection LED
PIR Lens
Relay 2 Mode
Audible Alert
Enabled
Disabled
9
Relay 1 Mode
Manual On
Auto On
PW-200 ONLY
Relay 2 Mode
Manual On
Auto On
Factory Settings:
All models
PW-100 series
1
PW-200 series
2
7