Sensor Operating Modes; Dip Switch Settings - LEGRAND Wattstopper PW Série Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Sensor #1 Sensor #2
Auto-ON
Auto-ON
Auto-ON*
Manual
ON*
Manual-
Manual-ON The occupant must press the ON/OFF button on either one of the sensors to turn the light ON. The sensors
ON
* Although this configuration may be selected, it is not recommended.
Tabs
Button
Hinges
PW-302 shown.
PW-301 has a
single button.
Lights do not turn ON with motion (LED does flash)
1. Press and release each button to make sure that the correct lights come ON for each relay. If the lights do NOT turn ON, check
wire connections, especially the Load connection. If the lights turn ON, verify that the correct ON Mode is selected in
DIP Switches 8 and 9.
2. Check to see if light level control is enabled: cover the sensor lens with your hand. If the lights come ON, adjust the light level
setting.
3. If lights still do not turn ON, call 800.879.8585 for technical support.
Lights do not turn ON with motion (LED does not flash)
1. Press and release each button to make sure that the correct lights come ON for each relay. If the lights turn ON, verify that
Sensitivity is on High.
2. Check the wire connections, in particular, the Line connection. Verify that connections are tightly secured.
3. If lights still do not turn ON, call 800.879.8585 for technical support.

SENSOR OPERATING MODES

The load turns ON and OFF automatically based on occupancy detection by either one of the sensors. The
sensors keep the load ON until no motion is detected and will use the time delay of the sensor with the
lowest value. At any time, the light can be turned ON and OFF using the ON/OFF button of any one of the
sensors. If the load is turned OFF manually by pressing either one of the ON/OFF buttons, the unit will enter
Presentation mode.
The load can only be turned ON automatically by the sensor set in Auto ON mode. The sensors keep the
load ON until no motion is detected and will use the time delay of the sensor with the lowest value. There is
either a 30 second re-trigger delay for the sensor set in Manual ON mode or instant re-trigger for the sensor
set in Auto ON mode. After the re-trigger delay elapses, the ON/OFF button of the sensor set in Manual
ON mode must be pressed to turn the load back on unless the sensor set in Auto ON mode detects motion.
If the light is turned ON manually by pressing the ON/OFF button set in Auto ON, it will enter Presentation
Mode.
keep the load ON until no motion is detected and will use the time delay of the sensor with the lowest value.
There is a 30 second re-trigger delay, meaning the occupant has 30 seconds to be detected for the sensor
to turn the load back on automatically. After the re-trigger delay elapses, the
ON/OFF button of any one of the sensors must be pressed to turn the load back ON.

DIP SWITCH SETTINGS

ON/OFF Buttons
Relay 1
Relay 2
Dip Switches
Detection LED
PIR Lens
Light Fixture
1 2 3
Time Delay
Test/20 min
5 minutes
10 minutes
15 minutes
20 minutes
25 minutes
30 minutes
Service
4
Walk-Through
Enabled
Disabled
Service bypasses occupancy
& light level functions. Control the
load manually using ON/OFF button.
TROUBLESHOOTING
5
Relay 1 Mode
Time
Visible
Relay 2 Mode
Delay
Alerts
ON
1
2
3
4
5
6
7
8
9
Walk-Through
Audible Alerts
PIR Sensitivity
5
PIR Sensitivity
Low, 50%
High
6
Visible Alert
Enabled
Factory Settings:
Disabled
1
=ON =OFF
2
7
Audible Alert
Enabled
Disabled
8
Relay 1 Mode
Manual On
1
Auto On
2
PW-302 ONLY
9
Relay 2 Mode
Manual On
Auto On
All models
PW-301 series
PW-302 series