Gray shaded cells in the following tables indicate the default operation and switch settings.
Presentation Mode
This mode is a feature of the Auto ON mode. When both relays are manually turned OFF the PW holds the lights OFF until no motion
has been detected for the duration of the Time Delay. With subsequent occupancy, the PW turns the load ON. If both relays are ON and
one relay is manually turned OFF this relay remains OFF until both the Time Delay and re-trigger delay expires for the relay that is ON,
after that time the ON Mode control settings again apply.
Time Delays
The PW sensor holds the load ON until no motion is detected for the selected time delay. Select the time delay using DIP switch
settings. In the PW-200, both relays use the same delay.
Test/20 min
(DIP 1, 2, 3, OFF)
Fixed Time Delay
(DIP 1 ON, 2 & 3 OFF)
Walk Through
The Walk-Through mode shortens the time delay to reduce the amount of time the load is ON after a brief moment of occupancy, such
as returning to an office to pick up a forgotten item then immediately exiting.
Walk-Through Mode
(DIP #4 ON)
No Walk-Through
(DIP #4 OFF)
PIR Sensitivity Adjustment
The PW sensor constantly monitors the controlled environment and automatically adjusts the PIR to avoid common ambient conditions
that can cause false detections, while providing maximum coverage.
High
(DIP #5 OFF)
Low, 50%
(DIP #5 ON)
Alerts
The PW can provide audible and/or visible alerts as a warning before the load turns OFF.
Visible Alert
(DIP #6 ON)
No Visible Alerts
(DIP #6 OFF)
Audible Alerts
(DIP #7 ON)
No Audible Alerts
(DIP #7 OFF)
RELAY
DEFAULT ON MODE
1
MANUAL ON
1
MANUAL ON
1
AUTO ON
2
MANUAL ON
1
AUTO ON
2
MANUAL ON
A Test Mode with a short time delay of 5 seconds is set when DIP switches 1, 2, & 3 are OFF. It cancels
automatically after ten minutes, or when you set a fixed time delay. When the Test Mode times out, the
sensor assumes a 20 minute time delay. To restart Test Mode, change the time delay setting to any fixed
amount and then return it to the Test setting.
Time delays are 5, 10, 15, 20 (default), 25, or 30 minutes.
The PW sensor turns the load OFF three minutes after the area is initially occupied, if no motion is
detected after the first 30 seconds. If motion continues beyond the first 30 seconds, the set time delay
applies.
Walk-Through mode disabled.
Default setting. Suitable for most applications.
Reduces sensitivity by approximately 50%. Useful in cases where the PIR is detecting movement
outside of the desired area (also consider masking the lens) and where heat sources cause unnecessary
activation.
When only one minute is left in the time delay, the load connected to the relay turns OFF for one second.
This provides a one minute warning before the load(s) are turned OFF by the sensor.
No visible warnings provided.
Unit will beep at one minute*, at 30 seconds and at 10 seconds before turning OFF load. When Walk-
Through is active, the unit beeps three times at 10 seconds before the load goes OFF.
*If Visible Alert is also ON, the one-minute time-out warning beep is replaced by the visible alert.
No audible warnings provided.
DIP SWITCH
SETTING
8
ON
8
ON
8
OFF
9
ON
8
OFF
9
ON
2