7. Starting, operation

Electrical connection

Connect the instrument to earth via the pressure connection.
Operate the pressure transmitter with a shielded cable and earth the shield at least on
one side of the cable.
Use power supplies which guarantee reliable electrical isolation of the operating
voltage as per IEC/DIN EN 60204-1. Consider also the general requirements for PELV
circuits in accordance with IEC/DIN EN 60204-1.
Ingress protection per IEC 60529 (The ingress protection classes specified only apply
while the pressure transmitter is connected with female connectors that provide the
corresponding ingress protection).
PIN assignment of connections according to CiA-DR 0-1
Circular connector
M 12x1, 5 pin, male
IP 67
Order code: M5
With integrated Y-piece
Circular connector
M 12x1, 5 pin, male
Circular connector
M 12x1, 5 pin, female
IP 67
Order code: 2M
8
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi/Instrucciones de servicio D-2X-9
GB
1 – Screen
2 – UB+ (CAN V+)
3 – UB- (CAN GND)
4 – Bus-Signal CAN-High
5 – Bus-Signal CAN-Low
1 – Screen
2 – UB+ (CAN V+)
3 – UB- (CAN GND)
4 – Bus-Signal CAN-High
5 – Bus-Signal CAN-Low
1 – Screen
2 – UB+ (CAN V+)
3 – UB- (CAN GND)
4 – Bus-Signal CAN-High
5 – Bus-Signal CAN-Low
7. Starting, operation
Specifications
Model D-20-9, D-21-9
Pressure ranges
bar
Over pressure safety
bar
Burst pressure
bar
Pressure ranges
bar
Over pressure safety
bar
Burst pressure
bar
{Vacuum, gauge pressure, compound range, absolute pressure are available}
Only Model D-20-9.
1)
2)
For model D-21-9: the value specified in the table applies only when sealing is
realised with the sealing ring underneath the hex. Otherwise max. 1500 bar applies.
Materials
Wetted parts
»
Model D-20-9
*)
»
Model D-21-9
Case
Internal transmission fluid
3)
Not for D-20-9 with pressure ranges > 25 bar
3)
Power supply U
U
in VDC
B
B
Signal output
Power input
W
Communication services
Filter
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi/Instrucciones de servicio D-2X-9
0.25
0.4
0.6
1
1.6
2.5
4
2
2
4
5
10
10
17
2.4
2.4
4.8
6
12
12
20.5
25
40
60
100
160
250
400
50
80
120
200
320
500
800
96
400
550
800
1000 1200 1700
2)
(Other materials see WIKA diaphragm seal program)
Stainless steel
Stainless steel {Hastelloy}
O-ring: NBR {FPM/FKM or EPDM}
Stainless steel
Synthetic oil {Halocarbon oil for oxygen applications}
{Listed by FDA for Food and Beverage}
≤ 30
10 < U
B
CANopen protocol acc. to CiA DS-301 V. 4.02,
Device profile DS-404 V. 1.2
< 0.5 {with galvanic isolation < 0.7}
LSS (CiA DSP 305, Version 1.1.1) Services
Configuration of device address and baud rate
Sync/Async, Node/Lifeguarding, Heartbeat
Individually programmable filter, to eliminate e. g. resonance frequen-
cies
GB
6
10
16
35
35
80
42
42
96
600
1000
1)
1200 1500
2400
2)
3000
9