SELECTION OF THE MODES AND CONTROL PANEL FUNCTIONS (SW2)
Using SW2, choose the required options:
1 DIP1: access to programming
DIP1=ON: programming mode.
DIP1=OFF: operation mode.
2 DIP2: operation warning
DIP2=ON: the lamp lights up and the operation
begins after a 3 second warning.
DIP2=OFF: the lamp lights up and the operation
begins immediately.
3 DIP9: type of flashing lamp
DIP9=OFF: the output for the lamp is static
(requires flashing lamp).
DIP9=ON: the output for the lamp is flashing
(requires static lamp).
4 DIP3: opening mode
DIP3=ON: step-by-step mode (the control
panel obeys the command during opening).
DIP3=OFF: community mode (the control
panel does not obey the command during opening).
7

TORQUE (FORCE) ADJUSTMENT

PROGRAMMING AND STARTING UP
5 DIP4: closing mode
DIP4=ON: Automatic mode (the gate closes
automatically after the waiting time).
DIP4=OFF: Semiautomatic mode (the gate
only closes when receiving the command).
Waiting time is adjusted by way of PT3.
6 DIP6: optional automatic mode (only if
DIP4=ON)
DIP6=ON: during waiting, the gate obeys the
transmitter (this can be closed using the transmitter
before waiting time finishes).
DIP6=OFF: the gate cannot be closed until the
waiting time finishes.
7 DIP5: back pulse
DIP5=ON: back pulse enabled (when opening
begins, there is a small backward movement of the
leaf in order to help release the interlocking of the
electrolock).
DIP5=OFF: back pulse disabled.
8 DIP7: one or two motors
DIP7=ON: operation of two motors.
DIP7=OFF: operation of a single motor.
9 DIP8: slow down function
DIP8=ON: the motors reduce their speed before
reaching the stopper.
DIP8=OFF: the motors reach the stopper at the
maximum programmed speed.
The
maximum
speed
programmed using the potentiometer V.M.
DIP10 no use.
Open gate waiting time (T.E.)
If automatic or optional automatic operation mode
has been programmed, regulate T.E. to adjust the
waiting time with the gate open (before automatic
closing begins).
Minimum value: 4 seconds; maximum value: 100
seconds.
Garage lighting time (T.LG)
If the garage lighting circuit has been connected to
the control panel, regulate the time which the lamps
shall remain on using T.LG.
Minimum value: 3 seconds; maximum value: 90
seconds.
of
the
motors
is
51