Wilo Control SC-Fire Diesel A2P Notice De Montage Et De Mise En Service page 52

Masquer les pouces Voir aussi pour Control SC-Fire Diesel A2P:
Table des Matières

Publicité

12 Annexes
Calcul de capacité des batteries
Consommation en veille sans
alimentation 230 VAC
Désignation
dans le
Désignation des composants
schéma
7K2
BC6-22-00, 24VDC
8G1
Signal converter SC-Fire
11G1
Signal converter SC-Fire
2U1
CPU SC-Fire ED
2U2
CPU SC-Fire ED
2xUM, 12VDC, 240VAC, 6A
10K1
2xUM, 24VDC, 240VAC, 6A
2xUM, 12VDC, 240VAC, 6A
10K2
2xUM, 24VDC, 240VAC, 6A
2xUM, 12VDC, 240VAC, 6A
10K3
2xUM, 24VDC, 240VAC, 6A
2xUM, 12VDC, 240VAC, 6A
10K4
2xUM, 24VDC, 240VAC, 6A
2xUM, 12VDC, 240VAC, 6A
10K5
2xUM, 24VDC, 240VAC, 6A
2xUM, 12VDC, 240VAC, 6A
10K6
2xUM, 24VDC, 240VAC, 6A
Buzzer 12VDC
10H1
Buzzer 24VDC
10K7
BC6-30-10, 24VDC
LCD-Panelmeter, EX2071, 0-
14P1
199,9V
LCD-Panelmeter, EX2070, 0-
14P2
19,99V
15P1
06000002, 12V, Ø56mm
06000003, 40-120°C, 12V,
15P2
Ø56mm
15P3
06000006, 0-8bar, 12V, Ø56mm
15P4
12V, Ø90,5mm
Consommation sans alimentation
P=28W (29W)
230V
U=12V
(24VDC)
Tension des batteries
h=72h
Temps requis pour le fonctionnement en autonomie
WILO SE 11/2016
Mesure
15mA sous 12,6Vdc 0,19 W
15mA sous 12,6Vdc 0,19 W
390mA sous 24Vdc
390mA sous 24Vdc
0,019A sous 12Vdc
0,008A sous 24Vdc
Total :
37��
�� =
12��
37��
�� =
∗ 72ℎ = 222��ℎ
12��
Consommation
Consommation
(sous 12V)
(sous 24V)
3,50 W
3,50 W
0,19 W
0,19 W
9,36 W
9,36 W
9,36 W
9,36 W
0,40 W
0,40 W
0,40 W
0,40 W
0,40 W
0,40 W
0,40 W
0,40 W
0,40 W
0,40 W
0,40 W
0,40 W
0,23 W
0,19 W
3,50 W
3,50 W
0,04 W
0,08 W
0,04 W
0,08 W
2,00 W
2,00 W
2,00 W
2,00 W
2,00 W
2,00 W
2,00 W
2,00 W
37 W
37 W
�� =
37��
�� =
24��
222Ah requis sur
111Ah requis sur
2 batteries
2 batteries
2x 111Ah
2x 56Ah
sous 12V
sous 24V
Français
37��
24��
∗ 72ℎ = 111��ℎ
52