potential measured by EES Pro, this is the set point. If a regular drift from the Redox value is noticed, or if
there is a sudden change in this value, replace the Redox sensor.
!
ATTENTION
The Redox system does not allow precise regulation of the free Chlorine concentration
at high set point values (above 2 ppm, that is approximately 725 mV at pH = 7.4).
8.4
Turbo mode
The Turbo
function allows continual production of Chlorine at maximum output (100%) over a duration
set by the user.
Press the
button to switch to Turbo mode: the word Turbo blinks at the bottom of the output scale.
The Turbo mode duration is set to 12 hours in the factory, this setting is displayed on screen.
Successive presses on the T button will increase the duration in increments of 12 hours up to a maximum
duration of 72 hours (then returns to 0).
For finer adjustment, in intervals of one minute, use the arrow keys, ▲ and ▼.
EXAMPLE:
To activate Turbo mode for a duration of 26 hours and 30 minutes. After having activated Turbo mode,
press the T button once -> 24:00 is displayed. To set the minutes, keep the ▲ key pressed down (rapid
scroll) and then press successively until 26:30 is displayed. If the value is overshot, use the ▼ key to return
to the desired value.
Next, the displayed time will start to count down, this represents the time remaining for the Turbo cycle.
!
IMPORTANT
begin setting the duration of the Turbo cycle with the T button within 5 seconds of
entering Turbo mode. Each successive press on the T button to modify the length of the cycle must
occur within 5 seconds of the last. Otherwise, pressing the T button will cause the device to exit Turbo
mode.
There are 3 ways to exit Turbo mode:
•
allow more than 5 seconds to elapse and then press the T button.
•
stop the device using the ON/OFF button
•
set the duration of the cycle to 00 : 00
Neither activation nor exiting Turbo mode will effect settings in AUTO mode.
!
IMPORTANT
Even in Turbo mode, the device will not run with an output of 100% if the salt concentration
in the water is too low. It will run at its highest possible output for the current concentration of salt in
the water.