Wilo Stratos MAXO Notice De Montage Et De Mise En Service page 9

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

▪ Closed industrial circulation systems
▪ Solar installations
▪ Geothermal systems
▪ Air-conditioning systems
The pumps do not fulfil the requirements of the ATEX guideline and
are not suitable for the pumping of explosive or easily flammable
fluids!
Proper intended use also includes compliance with these instruc-
tions in addition to the information and labels on the pump.
Any other use is regarded as improper use and results in the loss of
all liability claims.
Approved fluids
▪ Heating water according the requirements of accepted standards of
water quality in heating systems.
▪ Water-glycol mixture, max. mixing ratio 1:1
The pump delivery rate will be affected by the addition of glycol
due to the altered viscosity. Please take this into consideration
when adjusting the pump.
▪ Ethylene/propylene glycols with corrosion protection inhibitors.
▪ No oxygen binding agents, no chemical sealants (ensure system is
enclosed in terms of corrosion); repair leaking locations.
▪ Standard commercial corrosion protection inhibitors
rosive anodic inhibitors (under-dosing due to consumption!).
▪ Standard commercial corrosion protection inhibitors
ganic or polymer filming agents.
▪ Standard commercial cooling brines
Installation and operating instructions Wilo-Stratos MAXO /-D/-Z
1)
without cor-
1)
without inor-
1)
.
WARNING
Injuries to people and material damage caused
by unauthorized fluids!
Unauthorized fluids can cause injuries to people and
can destroy the pump.
1)
Always mix additives into the fluid on the pressure side of the
pump, even when contrary to the additive manufacturer's recom-
mendations.
▪ Only use branded goods with corrosion prevention inhibitors!
▪ Observe chloride content of filling-up water in accordance with
manufacturer's specifications! Soldering pastes containing chloride
are not permitted!
▪ Safety data sheets and manufacturers' specifications must be ob-
served!
Saline fluids
CAUTION
Material damage caused by saline fluids!
Saline fluids (e.g. carbonates, acetates or formates) are ex-
tremely corrosive and can destroy the pump!
▪ Fluid temperatures over 104 °F (40 °C) are not permitted for saline
fluids!
▪ Use a corrosion inhibitor and constantly check its concentration!
en-US
9

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Stratos maxo-dStratos maxo-z

Table des Matières