Johnson Controls 3G4010 V4.0 Manuel D'installation page 27

Table des Matières
Les langues disponibles

Les langues disponibles

Wiring diagrams
Figure 5: Wiring Diagram for Fire Alarm Control Unit (with dialler) and Cellular Transmitter (Passive
Communication System)
Power for the 3G4010/LE4010/LE4010E shall be provided from the Fire Alarm Control Unit or separately listed
power supply rated for the application (12V/700mA).
All wiring connections must be run in a protective conduit.
For local supervision of the wireless transmitter, connect PGM output from 3G4010/LE4010/LE4010E to one zone
input on the Fire Alarm Control Unit.
Dry Contact Trouble output from ULC Listed Fire Alarm Control Unit must be connected to zone input on the
3G4010/LE4010/LE4010E for supervison of Tip/Ring connection.
Fire Alarms must be sent over both communication channels. Fire output from Fire Alarm Control Unit must be
connected to input 1 on the 3G4010/LE4010/LE4010E.
24 hour Test Transmission must be enabled on the dialler and on the 3G4010/LE4010/LE4010E.
Figure 6: DSC Subscribers' Unit Fire and Cellular Transmitter Mounted in the Same Room
3G4010 V4.0 / LE4010 V5.1 / LE4010E V5.1 Installation manual
27
© 2025 Johnson Controls. All Rights Reserved.

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Le4010 v5.1Le4010e v5.1Dsc 3g4010cfDsc le4010cfDsc le4010ecf

Table des Matières