Wiring diagrams
Figure 5: Wiring Diagram for Fire Alarm Control Unit (with dialler) and Cellular Transmitter (Passive
Communication System)
Power for the 3G4010/LE4010/LE4010E shall be provided from the Fire Alarm Control Unit or separately listed
power supply rated for the application (12V/700mA).
All wiring connections must be run in a protective conduit.
For local supervision of the wireless transmitter, connect PGM output from 3G4010/LE4010/LE4010E to one zone
input on the Fire Alarm Control Unit.
Dry Contact Trouble output from ULC Listed Fire Alarm Control Unit must be connected to zone input on the
3G4010/LE4010/LE4010E for supervison of Tip/Ring connection.
Fire Alarms must be sent over both communication channels. Fire output from Fire Alarm Control Unit must be
connected to input 1 on the 3G4010/LE4010/LE4010E.
24 hour Test Transmission must be enabled on the dialler and on the 3G4010/LE4010/LE4010E.
Figure 6: DSC Subscribers' Unit Fire and Cellular Transmitter Mounted in the Same Room
3G4010 V4.0 / LE4010 V5.1 / LE4010E V5.1 Installation manual