Service Mode; Swinger Shutdown In Service Mode - Only Model Le4010/Le4010E; Operating Principles; Simulated Landline Mode - Johnson Controls 3G4010 V4.0 Manuel D'installation

Table des Matières
Les langues disponibles

Les langues disponibles

Operating principles

Service mode

To view detailed trouble information on the status LEDs, place the 3G4010/LE4010/LE4010E in Service mode by
removing the front cover. When in Service mode, the status LEDs indicate troubles as follows.
Table 4: LED troubles
Number of flashes
Red
1
2
3
1
2
3
1
2
3
4
OFF

Swinger shutdown in service mode - only model LE4010/LE4010E

When service mode is activated by opening the case tamper, swinger shutdown states are cleared. Swinger
shutdown will not be applied to any zone inputs while service mode is active.
Operating principles

Simulated landline mode

The simulated landline provides the alarm control panel (with dialer interface) with a backup line in the event of
PSTN line trouble.
Note: The 3G4010/LE4010/LE4010E must be programmed as a backup communicator for Simulated Landline
mode to operate.
If the voltage on the landline terminals (TIP/RNG) drops below 2.8V for a period of between 10 and 45 seconds -
depending on the alarm control panel connected to the T1/R1 terminals- the 3G4010/LE4010/LE4010E switches
the connected telephone device to the cellular network. After waiting between 30 and 40 seconds, it checks the
landline for one of the following:
If the landline has been restored, the 3G4010/LE4010/LE4010E switches the connected device back to the
landline, OR
If the landline is still down, the 3G4010/LE4010/LE4010E continues the simulation until the landline is restored.
The 3G4010/LE4010/LE4010E will not switch during ongoing calls.
Note: When the landline is down, the 3G4010/LE4010/LE4010E provides a dial tone to any device connected to
T1 and R1, including any telephones on the premises. The phones on the premises are not, however, able to
dial out over the 3G4010/LE4010/LE4010E.
3G4010 V4.0 / LE4010 V5.1 / LE4010E V5.1 Installation manual
Troubles
Blue
OFF
Wireless network trouble - unable to connect to cellular network
OFF
Battery trouble - battery with low voltage output
OFF
Input power trouble
FLASHING
Insufficient signal strength - poor location
FLASHING
C24 suppressed trouble
FLASHING
C24 communication configuration trouble
ON
Radio/SIM trouble - radio or SIM unresponsive
ON
Receiver not available trouble
ON
Supervision trouble
ON
Cover tamper is open
-
No trouble