Operating principles
After the 3G4010/LE4010/LE4010E generates a kiss-off signal, it sends the next alarm or, if no further alarms
need to be sent, the control panel goes on hook.
Note: The 3G4010/LE4010/LE4010E automatically adjusts the order of the handshakes based on the last
format the control panel used to transmit an event.

Inputs

The 3G4010/LE4010/LE4010E has four inputs that can be used to trigger specific communications. These events
transmit using the Contact ID or SIA format with Inputs 1-4 reporting as [991] to [994] respectively.
Default settings are:
INPUT 1- FIRE
INPUT 2 - PANIC ALARM
INPUT 3 - BURGLARY
INPUT 4 - SYSTEM TROUBLE
Inputs can be configured as follows:
Normally Open - input activates when a short condition is detected between the terminal and COM
Normally Closed - input activates when an open condition is detected between the terminal and COM
Single End of Line - input activates when a short or open condition is detected between the terminal and COM and
restores when a 5.6Kohm resistor is detected between the terminal and COM.
Note: These inputs are programmable to communicate using either the Contact ID or SIA format.
Note: For UL/ULC installations, connections between alarm panel outputs and 3G4010/LE4010/LE4010E inputs
must be run in protective mechanical conduits. To reduce interference with the antenna, do not connect metal
conduit to the knock-outs in the top of the cabinet.

Outputs

The 3G4010/LE4010/LE4010E has four programmable outputs to activate in response to the associated events.
Refer to the 3G4010/LE4010/LE4010E Wiring Diagram at the back of this manual.

Activating the outputs

The 3G4010/LE4010/LE4010E has four open collector outputs capable of a maximum of 50mA. Internal events on
the 3G4010/LE4010/LE4010E can trigger the outputs to turn on an LED or activate an input on the host panel. The
default settings are as follows.
OUTPUT 1: Landline Trouble - Output is normally high and switches to ground when the telephone line is down.
OUTPUT 2: Cellular Module or Network Trouble - Output is normally high and switches to ground when the
3G4010/LE4010/LE4010E cannot communicate with the network.
OUTPUT 3: Power Supply or Battery Trouble - Output is normally high and switches to ground when a problem
with the power source is detected.
OUTPUT 4: General Module Trouble - Output is normally low and switches to high when a Cellular Network
Trouble, Power Supply/Battery Trouble, and/or a Failure to Communicate (FTC) trouble is detected.
Note: PGM4 must be connected to the control panel as shown in Figure 4 (Residential applications) or Figures
8-9 (Commercial applications). Program the control panel input Zone/Point as 24hr 'Supervisory' with keypad
only notification when activated. Output 4 on the 3G4010/LE4010/LE4010E must be set as 'Active High'.
Note: Once an output has been activated automatically, it will not restore until all the causes of activation are
cleared.
3G4010 V4.0 / LE4010 V5.1 / LE4010E V5.1 Installation manual