Connecting the 3G4010/LE4010/LE4010E

Red
ON
When the 3G4010/LE4010/LE4010E sends a request to communicate with the next central station, the bottom
signal strength LED begins flashing.
Red
ON
When a signal is received from the central station, the bottom signal strength LED turns on solid.
Red
ON
If at least one of the central stations did not respond to the communicator, the signal strength LED corresponding
to that central station turns off. Once the initialization sequence completes, the 3G4010/LE4010/LE4010E begins
steady state operation.

Step 6 - Mount the 3G4010/LE4010/LE4010E

Note: Check for cable conduits and water pipes before drilling.
Note: Ensure that power and Telco circuit connections are made only after the cabinet has been secured
to the building or structure, and has been connected to the protective earth ground. Descriptions of the
terminals can be found in the 'Connecting the 3G4010/LE4010/LE4010E' section.
Note: Please refer to the end of this manual for wiring diagrams. The product is not to be installed outdoors
or outside the protected premises.
1. Power down the 3G4010/LE4010/LE4010E by removing the DC power source and battery leads.
2. Using the cabinet, mark the four screw locations. Drill the anchor screw holes.
3. Using anchor screws (not provided), mount the cabinet to the wall.
4. Run the cables through the cable entry [13] or through the cabinet knockouts.
5. Complete the connections on the terminal blocks [11].
6. Reattach the front cover [1] securely to the cabinet.
Connecting the 3G4010/LE4010/LE4010E
(1) Earth Ground - This terminal must be connected to the Mains Earth, in order to comply with the
Telecommunications Network Safety Standards (Overvoltage Protection Requirements).
TIP (2) / RNG (3) External Telephone Line - These terminals must be connected directly to the incoming
telephone line.
T1 (4) / R1 (5) Internal Telephone Line - These terminals must be connected to the TIP and RING of the control
panel.
COM (6,12) Common - This terminal is connected internally to Power Ground.
PGM1 (7), PGM2 (8), PGM3 (9), PGM4 (10) Programmable Open-collector Outputs - These outputs can be activated
by programmed events. Refer to 'Activating the Outputs' for details. The maximum current sink of each output
must not exceed 50mA.
AUX+ (11) Auxiliary Output - 9 to 14 VDC Output, 500mA PTC Protected.
3G4010 V4.0 / LE4010 V5.1 / LE4010E V5.1 Installation manual
Blue
ON
Blue
ON
Blue
ON
© 2025 Johnson Controls. All Rights Reserved.
Yellow / Green (High)
ON
Yellow / Green (High)
ON
Yellow / Green (High)
ON
Yellow / Green (Low)
OFF
Yellow / Green (Low)
FLASHING
Yellow / Green (Low)
ON
12